3100 Wood Stove Series (ACC)
A. Hearth Protection Requirements
FLOOR PROTECTION:
Floor protector must be non-com-
bustible material, extending beneath heater and to the front,
sides and rear as indicated. The fl oor must be non-com-
bustible or otherwise adequately protected from radiant heat
given off by the unit and from sparks and falling embers. A
layer of thin brick or ceramic tile over a combustible fl oor is
not suffi cient.
For the Millennium | Limited Edition Models In US instal-
lations,
it is necessary to install a fl oor protector of a minimum
of 3/8 inch (9.5mm) thick metal clad millboard or equivalent a
minimum of 16 inches (406mm) in front of glass and 8 inches
(203mm) to both sides of the fuel loading door. Open the
door and measure 8 inches (203mm) from the side edge of
the opening in the face of the appliance. *
See exception.
16 in. from glass
8 in.
Fuel loading door
31-5/8 in.
minimum
39 in.
minimum
203mm (8 in.)
203mm
(8 in.)
203mm
(8 in.)
457mm (18 in.)
1260mm
(49-5/8 in.)
minimum
1041mm (41 in.)
minimum
Must extend 2 in.
(51mm) beyond
each side of pipe
(shaded area)
In Canada,
similar fl oor protection must be provided 18
inches (457mm) in front and 8 inches (203mm) from the
sides and rear of the stove. *
See exception.
*EXCEPTION:
Non-combustible fl oor protections must
extend beneath the fl ue pipe when installed with horizontal
venting and extend 2 inches (51mm) beyond each side.
See Figure 12.2.
Figure 12.3
4
Installation
Figure 12.1
Figure 12.2
Figure 12.4
Millennium | Limited Edition Models
33-1/4 in.
38-15/
16 in.
3-1/1
6 in.
135°
opt
io
na
l
co
ve
rage
52-1/2 in.
31-5/8 in
60-5/8 in.
27-3/8 in.
USA
USA
CANADA
WARNING
Fire Risk.
• Hearth pads must be installed exactly as specifi ed
High temperatures or hot embers may ignite concealed
combustibles.
Corner hearth pad dimensions
with single wall pipe
27-
3/8 in.
31-3/4 in.
38
-15/
16 in.
3-1/
16 in.
13
5°
op
tional
co
ve
rage
51 in.
31-5/8 in
58-1/2 in
.
Corner hearth pad dimensions
with double wall pipe
NOTE: Corner hearth pad dimensions are based off of 18” min. clear-
ance for single wall pipe, 6” min. for double wall pipe, OR unit tested
safety clearances to combustibles whichever is greater.