MT VERNON E2

Vent Information

A.  Venting Termination Minimum Requirements

J or K

X

V

M

I

H

A

V

G

B

V

V

A

B

V

F

V

C

B

B

E

L

V

D

V

Electrical

Service

V

N

V

N

V

N

N

V

Inside Corner

FIXED 
CLOSED

OPEN

OPEN

FIXED 
CLOSED

V

X

G

G

Termination Cap

Air Supply Inlet

Gas Meter

Restricted Area

O

P

Figure 10.1

A

12 in.

Above Finish Grade (the grade surface 
must be a non-combustible material

B

12 in.
48 in. no OAK

Open door or window: below or to the side

B

12 in.

Open door or window: above

C

6 in.

Permanently closed window: above, below 
or to the side

D

18 in.
36 in. no OAK

Vertical clearance to a ventilated soffi t 
located above the terminal within a hori-
zontal distance of 2 ft from the center-line 
of the terminal 

E

12 in.

Clearance to unventilated soffi t

F

12 in.

Clearance to outside corner

G

12 in.

Clearance to inside corner

H

36 in.

Above gas meter/regulator measured from 
horizontal center-line of regulator

I

36 in. USA
72 in. Canada

Clearance to service regulator vent outlet

J

12 in.
48 in. no OAK

Clearance to non-mechanical air supply 
inlet to the building or the combustions air 
inlet to any other appliance

K

10 ft horizontal
3 ft vertical

Clearance to mechanical air supply

L

7 ft.

Above paved sidewalk, paved driveway 
located on 

public

 property

M

12 in.

Under an open veranda, porch, deck or 
balcony

N

See Note 
below*

Electric service: above, below or to the 
side (location must not obstruct or interfere 
with access)

O

24 in.

Adjacent building, fences and protruding 
parts of the structure

P

12 in.

Clearance above roof line for vertical 
terminations

All minimum clearances are listed with an Outside Air Kit (OAK) installed, unless otherwise noted in table below.

24 in.

Above grass, top of plants, wood or any other com-
bustible

12 in.
36 in. no OAK

Clearance from any forced air intake of other appli-
ance

12 in.

Clearance horizontally from combustible wall

15 in.

Vented directly through a wall, minimum length of 
horizontal pipe

6 in. horizontal
12 in. vertical

Minimum horizontal or vertical terminations must 
protrude from wall

*NOTE: 

 Consult local building, fi re offi cials or authorities having jurisdic-

tion.  Local codes or regulations may require different clearances.

NOTICE:

Do NOT Terminate Vent:

• 

In any location that will allow fl ue gases or soot from en-
tering  or staining the building

•  In any location which could create a nuisance or hazard

• 

In any enclosed or semi-enclosed area such as a carport, 
garage, attic, crawl space, under a sun deck or porch, 
narrow walkway 

•  Closely fenced area, or any location that can build up 

a concentration of fumes such as a stairwell, covered 
breezeway, etc.

NOTICE:

Termination must exhaust above air inlet elevation.  

•  It is recommended that at least 60 inches (1.52m) of ver-

tical pipe be installed when appliance is vented directly 
through a wall.  This will create a natural draft, which will 
help prevent the possibility of smoke or odor venting into 
the home during a power outage. 

•  It will also keep exhaust from causing a nuisance or hazard 

by exposing people or shrubs to high temperatures.  

•  The safest and preferred venting method is to extend the 

vent vertically through the roof or above the roof.

Summary of Contents for MTV-E2-CSB

Page 1: ...other flam mable vapors and liquids in the vicinity of this or any other appliance Do not overfire If heater or chimney con nector glows you are overfiring Overfiring will void your warranty Comply wi...

Page 2: ...B Remote Thermostat Location 5 C Tools And Supplies Needed 5 D Inspect Appliance and Components 5 E Install Checklist 6 3 Dimensions and Clearances 7 A Appliance Dimensions 7 B Clearances to Combusti...

Page 3: ...aterials reported as passing ASTM E 136 Standard Test Method for Behavior of Metals in a Vertical Tube Furnace of 750 C G Combustible Materials Material made of or surfaced with any of the following m...

Page 4: ...installation Location of the appliance and chimney will affect performance Consideration must be given to Safety convenience traffic flow Placement of the chimney and chimney connector and to minimize...

Page 5: ...mostat s location will have some affect on the appliance s operation When located close to the appliance it may require a slightly higher temperature setting to keep the rest of the house comfortable...

Page 6: ...responsible Installer Builder Other Trades etc and corrective action needed Comments communicated to party responsible by on Builder Gen Contractor Installer Date Part 4017 254 Rev B 01 29 13 E Instal...

Page 7: ...ure 7 5 Side View Figure 7 2 Side View with Top Vent Adapter and 3 to 6 in 76 152mm Offset Adapter 31 1 16 788 29 3 16 741 q 5 13 16 147 2 9 16 65 3 13 16 97 14 1 16 357 28 1 8 714 32 5 16 821 28 7 16...

Page 8: ...e when installed with horizontal venting or under the Top Vent Adapter with vertical installation CANADA INSTALLATIONS A non combustible floor pro tection extending beneath the flue pipe is required w...

Page 9: ...lustrations diagrams are not drawn to scale Actual installation may vary due to individual design preference D Alcove Figure 9 1 All minimums listed are to a combustible surface Minimum Maximum Inches...

Page 10: ...nd protruding parts of the structure P 12 in Clearance above roof line for vertical terminations All minimum clearances are listed with an Outside Air Kit OAK installed unless otherwise noted in table...

Page 11: ...he exhaust vent outlet and located lower on the wall than the exhaust vent outlet The outside air supply kit can supply most of the demands of the pellet appliance but consideration must be given to t...

Page 12: ...E Hearth Home Technologies assumes no responsibility for the improper performance of the chimney system caused by Inadequate draft due to environmental conditions Downdrafts Tight sealing construction...

Page 13: ...you may use 3 or 4 inch 76 to 102mm diameter type L or PL vent G Pipe Selection Chart The chart will help you in determining proper venting size according to the equivalent feet of pipe calculated pre...

Page 14: ...m Minimum 2 in 51mm Minimum 6 in 152mm Minimum 6 in 152mm Minimum 45 Degree 5 Venting Systems A Through The Wall Horizontal termination cap must be a minimum of 6 inches 152mm from the wall Approved f...

Page 15: ...Minimum Rain Cap Flashing 3 in 76mm Min 6 in 152mm Min 3 to 3 in 76 to 76mm Top Vent Kit Clean out Cover Figure 15 3 We recommend a minimum of 60 inches 1524mm vertical however above the eave is prefe...

Page 16: ...mm clearance with firestop Figure 16 1 Figure 16 2 Concrete Cap Non combustible Hearth Pad 6 in 152mm Min Airtight clean out door Sheathing 1 in 25mm clearnance Flashing Fireclay Flue Liner with airsp...

Page 17: ...INCLUDED Tools Needed Phillips head screw driver wire cutters hole saw or jig saw 1 Measure distance from floor to air vent opening in appli ance and mark location on wall Use saw to cut opening in w...

Page 18: ...nstall the 5 mounting screws 3 on the left and 2 on the right 5 Drill 2 holes with 26 drill bit through the rear exhaust outlet using the 2 holes already in the short horizontal pipe in the top vent a...

Page 19: ...appliance warranty Figure 19 1 Log fits over screws Left Log Log has indentations on the bottom to fit over the screw heads Log rests in front of screws Right Log Figure 19 3 Figure 19 4 E Optional L...

Page 20: ...ll bit Tape Measure Detach the remote thermostat from its docking station by pulling them directly away from each other Using the fasteners and if needed anchors included with the remote transmitter p...

Page 21: ...t 24 Part Number OAK 3 NEVER INSTALL IN A SLEEPING ROOM WARNING Spark Arrestor Cap Roof Flashing Storm Collar Joist Shield Firestop Approved Class L or PL Pellet Vent Figure 21 1 CAUTION Never draw ou...

Page 22: ...3 Y Damper 4 Inch Tall Vertical Installs Only PEL DAMP4 Firescreen No Longer Available SCR 7005 Log Set Sold as Set only 2 Pc LOGS 60 AE B Outside Air Kit OAK 3 Top Vent Adapter TPVNT 3 Warming Shelve...

Page 23: ...October 28 2014 7080 131D 23 MT VERNON E2...

Page 24: ...lville WA 99114 Division of HNI INDUSTRIES Please contact your Quadra Fire dealer with any questions or concerns For the number of your nearest Quadra Fire dealer log onto www quadrafire com This prod...

Reviews: