background image

 12 

 

 

 

 

                      

7080-131D 

 

 

 

           October 28, 2014

MT VERNON E2

C.  Negative Pressure

 

Negative pressure results from the imbalance of air avail-
able for the appliance to operate properly. It can be strongest 
in lower levels of the house.

Causes include:

•  Exhaust fans (kitchen, bath, etc.)

• Range 

hoods

•  Combustion air requirements for furnaces, water heaters 

and other combustion appliances

• Clothes 

dryers

•  Location of return-air vents to furnace or air conditioning

•  Imbalances of the HVAC air handling system

•  Upper level air leaks such as: 

 - 

Recessed 

lighting

 - 

Attic 

hatch

 - 

Duct 

leaks

To minimize the effects of negative air pressure:

•  Install the outside air kit with the intake facing prevailing 

winds during the heating season

• 

Ensure adequate outdoor air for all combustion appliances 
and exhaust equipment

•  Ensure furnace and air conditioning return vents are not 

located in the immediate vicinity of the appliance

•  Avoid installing the appliance near doors, walkways or 

small isolated spaces

•  Recessed lighting should be a “sealed can” design

•  Attic hatches weather stripped or sealed

• 

Attic mounted duct work and air handler joints and seams 
taped or sealed

D.  Draft 

Draft is the pressure difference needed to vent an appli-
ance successfully. When an appliance is drafting suc-
cessfully, all combustion byproducts are exiting the home 
through the chimney.

Install through the warm airspace enclosed by the build-
ing envelope. This helps to produce more draft, especially 
during lighting and die-down of the fi re.

Considerations for successful draft include:

•  Preventing negative pressure
•  Location of appliance and chimney

WARNING

Risk of Asphyxiation!

 

Negative pressure can cause spillage of combustion 
fumes and soot.

NOTICE:  Hearth & Home Technologies assumes no 
responsibility for the improper performance of the chimney 
system caused by:

•  Inadequate draft due to environmental conditions
• Downdrafts
•  Tight sealing construction of the structure
•  Mechanical exhausting devices

E.  Chimney and Exhaust Connection 

1.

 Chimney & Connector

:  Use 3 or 4 inch (76-102mm)  

diameter type “L” or “PL” venting system.  It can be vented 
vertically or horizontally.

WARNING

USE ONLY RECOMMENDED VENTING COMPONENTS; 
OTHERWISE MAKESHIFT PARTS MAY RESULT IN PROP-
ERTY DAMAGE, PERSONAL INJURY, OR DEATH. 

NOTE

: The appliance exhaust outlet is designed to ac-

commodate 3 inch venting. Use of 4 inch venting requires 
the use of a 3-to-4 inch exhaust vent increaser in addition 
to any other  venting components needed, sold separate-
ly.

2.

 Mobile Home: 

Approved for all Listed pellet vent.  If using 

the 3 inch (76mm) vertical Top Vent Adapter Kit or the 3 
to 6 inch (76-152mm) Top Vent Offset Adapter, use Listed 
double wall fl ue connector.  A Quadra-Fire Outside Air Kit 
(OAK-3) must be used with manufactured home installa-
tions.

3.

 Residential: 

 The 3 inch (76mm) vertical Top Vent Adapter 

Kit and the 3 to 6 inch (76-152mm) Top Vent Offset Adapter 
are tested to use 24 gauge single wall fl ue connector or 
Listed double wall fl ue connector to Class A Listed metal 
chimneys, or masonry chimneys meeting International 
Residential Code standards for solid fuel appliances.

4.

  INSTALL VENT AT CLEARANCES SPECIFIED BY THE 

VENT MANUFACTURER.

5.  Secure exhaust venting system to the appliance with at 

least 3 screws.  Also secure all connector pipe joints with 
at least 3 screws through each joint.

6.  DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST 

VENTING SYSTEM OF THIS UNIT.

7.  DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE 

SERVING ANOTHER APPLIANCE.

NOTE:  All pipe must be welded seam pipe whenever 
possible.  Seal pipe joints with high temperature silicone 
(500°F [260°C] minimum rated only).

Summary of Contents for MTV-E2-CSB

Page 1: ...other flam mable vapors and liquids in the vicinity of this or any other appliance Do not overfire If heater or chimney con nector glows you are overfiring Overfiring will void your warranty Comply wi...

Page 2: ...B Remote Thermostat Location 5 C Tools And Supplies Needed 5 D Inspect Appliance and Components 5 E Install Checklist 6 3 Dimensions and Clearances 7 A Appliance Dimensions 7 B Clearances to Combusti...

Page 3: ...aterials reported as passing ASTM E 136 Standard Test Method for Behavior of Metals in a Vertical Tube Furnace of 750 C G Combustible Materials Material made of or surfaced with any of the following m...

Page 4: ...installation Location of the appliance and chimney will affect performance Consideration must be given to Safety convenience traffic flow Placement of the chimney and chimney connector and to minimize...

Page 5: ...mostat s location will have some affect on the appliance s operation When located close to the appliance it may require a slightly higher temperature setting to keep the rest of the house comfortable...

Page 6: ...responsible Installer Builder Other Trades etc and corrective action needed Comments communicated to party responsible by on Builder Gen Contractor Installer Date Part 4017 254 Rev B 01 29 13 E Instal...

Page 7: ...ure 7 5 Side View Figure 7 2 Side View with Top Vent Adapter and 3 to 6 in 76 152mm Offset Adapter 31 1 16 788 29 3 16 741 q 5 13 16 147 2 9 16 65 3 13 16 97 14 1 16 357 28 1 8 714 32 5 16 821 28 7 16...

Page 8: ...e when installed with horizontal venting or under the Top Vent Adapter with vertical installation CANADA INSTALLATIONS A non combustible floor pro tection extending beneath the flue pipe is required w...

Page 9: ...lustrations diagrams are not drawn to scale Actual installation may vary due to individual design preference D Alcove Figure 9 1 All minimums listed are to a combustible surface Minimum Maximum Inches...

Page 10: ...nd protruding parts of the structure P 12 in Clearance above roof line for vertical terminations All minimum clearances are listed with an Outside Air Kit OAK installed unless otherwise noted in table...

Page 11: ...he exhaust vent outlet and located lower on the wall than the exhaust vent outlet The outside air supply kit can supply most of the demands of the pellet appliance but consideration must be given to t...

Page 12: ...E Hearth Home Technologies assumes no responsibility for the improper performance of the chimney system caused by Inadequate draft due to environmental conditions Downdrafts Tight sealing construction...

Page 13: ...you may use 3 or 4 inch 76 to 102mm diameter type L or PL vent G Pipe Selection Chart The chart will help you in determining proper venting size according to the equivalent feet of pipe calculated pre...

Page 14: ...m Minimum 2 in 51mm Minimum 6 in 152mm Minimum 6 in 152mm Minimum 45 Degree 5 Venting Systems A Through The Wall Horizontal termination cap must be a minimum of 6 inches 152mm from the wall Approved f...

Page 15: ...Minimum Rain Cap Flashing 3 in 76mm Min 6 in 152mm Min 3 to 3 in 76 to 76mm Top Vent Kit Clean out Cover Figure 15 3 We recommend a minimum of 60 inches 1524mm vertical however above the eave is prefe...

Page 16: ...mm clearance with firestop Figure 16 1 Figure 16 2 Concrete Cap Non combustible Hearth Pad 6 in 152mm Min Airtight clean out door Sheathing 1 in 25mm clearnance Flashing Fireclay Flue Liner with airsp...

Page 17: ...INCLUDED Tools Needed Phillips head screw driver wire cutters hole saw or jig saw 1 Measure distance from floor to air vent opening in appli ance and mark location on wall Use saw to cut opening in w...

Page 18: ...nstall the 5 mounting screws 3 on the left and 2 on the right 5 Drill 2 holes with 26 drill bit through the rear exhaust outlet using the 2 holes already in the short horizontal pipe in the top vent a...

Page 19: ...appliance warranty Figure 19 1 Log fits over screws Left Log Log has indentations on the bottom to fit over the screw heads Log rests in front of screws Right Log Figure 19 3 Figure 19 4 E Optional L...

Page 20: ...ll bit Tape Measure Detach the remote thermostat from its docking station by pulling them directly away from each other Using the fasteners and if needed anchors included with the remote transmitter p...

Page 21: ...t 24 Part Number OAK 3 NEVER INSTALL IN A SLEEPING ROOM WARNING Spark Arrestor Cap Roof Flashing Storm Collar Joist Shield Firestop Approved Class L or PL Pellet Vent Figure 21 1 CAUTION Never draw ou...

Page 22: ...3 Y Damper 4 Inch Tall Vertical Installs Only PEL DAMP4 Firescreen No Longer Available SCR 7005 Log Set Sold as Set only 2 Pc LOGS 60 AE B Outside Air Kit OAK 3 Top Vent Adapter TPVNT 3 Warming Shelve...

Page 23: ...October 28 2014 7080 131D 23 MT VERNON E2...

Page 24: ...lville WA 99114 Division of HNI INDUSTRIES Please contact your Quadra Fire dealer with any questions or concerns For the number of your nearest Quadra Fire dealer log onto www quadrafire com This prod...

Reviews: