October 28, 2014
7080-131D
15
MT VERNON E2
C. Through The Wall & Vertical - Exterior
Firestop
Flashing
Rain Cap
6 in
[152mm]
Min
Non-combustible Hearth Pad
3 in [76mm] Min
Clean-out Cover
12 in. [305mm] Min
Ceiling Support
3 to 6 in [76 to 152mm]
Offset Adapter
6 in. [152mm] Class A
Chimney Connector
Adapter
3 to 3 in
[76-76mm]
Top Vent Kit
Non-combustible Hearth Pad
Clean-out
Cover
Tee
Wall Thimble
Support
Bracket
every 60 in
[1524mm]
12 in
[305 mm]
Minimum
Rain
Cap
Flashing
2 in [51mm] min
6 in
[152mm]
Min
Figure 15.1
Figure 15.2
D. Vertical - Interior - Typical Installation
Firestop
Non-combustible Hearth Pad
12 in
[305 mm]
Minimum
Rain
Cap
Flashing
3 in [76mm] Min
6 in
[152mm]
Min
3 to 3 in
[76 to 76mm]
Top Vent Kit
Clean-out Cover
Figure 15.3
We recommend a minimum of 60 inches
(1524mm) vertical, however above the eave
is preferred.
All three installations are approved for mobile
home installations. Must use 3 or 4 inch (76
to 102mm) “L” or “PL” Listed pellet venting or
Listed double wall pipe and Quadra-Fire Outside
Air Kit in mobile homes. Single wall pipe is
approved for residential installations only.
*NOTE: Clearance to combustibles are for
standard pellet pipe. If pellet pipe manufacturer
allows reduced clearances to their pipe, reduced
clearances are allowed.
B. Vertical into Existing Class A Chimney
NOTE:
A chimney connector shall not pass through
an attic or roof space, closet or similar
concealed space, or a fl oor or ceiling.