18
B. Mantel and Wall Projections
WARNING! Risk of Fire!
Comply with all minimum clear-
ances to combustibles as speci
fi
ed. Framing or
fi
nishing
material closer than the minimums listed must be construct-
ed entirely of noncombustible materials (i.e., steel studs,
concrete board, etc).
Clearance to combustible material under the insert is 1/4
inch (6 mm). Clearance from top of
fi
replace opening for
combustibles extending 12 inches max. is 12 inches.
• Use leveling legs to raise insert minimum 1/4 inch (6 mm)
above combustible material or outer wrap of factory built
fi
rebox.
Combustible facings must not extend behind the insert
surround. For non-combustible material speci
fi
cations
refer to section 1.E.
Figure 5.3 Mantel Clearances
12 IN. MIN.
12 IN. MAX.
EXISTING NON-COMBUSTIBLE FACING
C
D
SURROUND
APPLIANCE
1-1/2 IN.
B
D
A
D
APPLIANCE
SURROUND
MINIMUM FIREPLACE SIZE
Location
QFI35
QFI30
Inches
Millimeters
Inches
Millimeters
A
D
Alternate Unit Width
33-3/16
843
29-1/16
738
B
D
Alternate Unit Depth
15-1/16
383
13-7/8
352
C
D
Alternate Unit Height
22-9/16
573
19-1/16
484
* Note: If exhaust collar on insert and fi replace damper do not line up, add 4 inches (102 mm) to minimum
fi replace height for bends in vent pipe.
TOP VIEW
SIDE VIEW
Figure 5.2 Fireplace Opening - Deep Surround