2700-I WOOD INSERT (ACT)
Page 10
September 1, 2008
R
7007-161H
The following modifications of factory-built fireplaces are
permissible: 1) removal of damper; 2) removal of smoke
shelf or baffle; ) removal of ember catches; 4) removal
of fire grate; 5) removal of viewing screen/curtain; and, 6)
removal of doors.
NOTE: Installation into fireplaces without a permit will
void the listing.
The factory-built chimney must be listed per UL 127 and
meet the type HT requirements of UL 10. Factory-built
fireplace chimneys tested to UL 127-1998, may be at the
fireplace manufacturer’s option, tested to the same criteria
as UL 10 HT requirements. If the chimney is not listed as
meeting HT requirements, or if the factory-built fireplace was
tested prior to 1998, a full height listed chimney liner must
be installed from the appliance flue collar to the chimney
top. The liner must meet type HT requirements (2100ºF)
per UL 1777.
The liner must be securely attached to the insert flue collar
and the chimney top. To prevent room air passage to the
chimney cavity of the fireplace seal the damper area around
the chimney liner with high temperature sealant.
The fireplace must not be altered, except that the damper
may be removed to accommodate a direct-connect starter
pipe or chimney liner, and external trim pieces which do not
affect the operation of the fireplace may be removed provid-
ing they can be stored on or within the fireplace for reas-
sembly if the insert is removed.
Direct Connect
Seal Option
Full Listed
Liner Option
Mantel
SEAL DAMpER AREA
Masonry
Chimney
Flue T
ile
Damper
Area
Figure 10.1 - Installation Into A Factory-Built Zero-Clearance
Fireplace
The Quadra-Fire 2700-I Insert is listed to UL 1482 Standard
and is approved for installation into listed factory-built zero
clearance fireplaces listed to UL 127 conforming to the follow-
ing specifications and instructions:
FACTORY BUILT ZERO CLEARANCE FIREpLACE
(USA INSTALLATIONS ONLy)
Minimum Width of Cavity Opening
28
711
Minimum Height
18-7/8
479
Minimum Depth from Front to Rear
17
42
Inches
Millimeters
The original factory-built clearance fireplace chimney cap
must be re-installed after installing the approved chim-
ney liner meeting type H.T. requirements (2100°F) per UL
1777. The air flow of the factory-built zero-clearance fire-
place system must not be altered. The flue liner top support
attachment must not reduce the air flow for the existing air-
cooled chimney system.
NOTE: Refer to chimney liner manufacturer for recom-
mendations on supporting the liner.
Fire Risk.
When lining air-cooled factory-built chimneys:.
• Run chimney liner approved to UL 1777 Type
HT requirements (2100 degrees F)
• Re-install original factory built chimney cap
ONLY
• DO NOT block cooling air openings in chimney
• Blocking cooling air will overheat the chimney
WARNING
The permanent metal warning label provided must be
attached to the back of the fireplace, with screws or nails,
stating that the fireplace may have been altered to accom-
modate the insert, and must be returned to original condition
for use as a conventional fireplace.
If the hearth extension is lower than the fireplace opening, the
portion of the insert extending onto the hearth must be sup
-
ported. Manufacturer designed adjustable support kit can be
ordered from your dealer.
See page 15.
Final approval of this installation type is contingent upon
the authority having jurisdiction.