Page 9
September 1, 2008
R
7007-161H
2700-I WOOD INSERT (ACT)
MASONRY FIREpLACE
USING DIRECT-CONNECT METHOD
Figure 9.1 - Installation Into Masonry Fireplace
Direct Connect
Seal Option
Full Listed
Liner Option
Mantel
SEAL DAMpER AREA
Masonry
Chimney
Flue T
ile
Damper
Area
The Quadra-Fire 2700-I Insert conforms with the UL Stan-
dard for Safety 1482 and ULC S628 (Canada) in all respects,
and is approved to UL & ULC safety standards for installa-
tion and use within a fireplace with a masonry chimney in
accordance with NFPA 211, with a direct flue collar connec-
tion. A starter pipe is required to reach to the bottom of the
existing flue.
1. Secure the fireplace damper in the open position. If this
cannot be accomplished, it will be necessary to remove
the damper.
2. Seal the damper area around the chimney liner with a
high temperature sealant.
. The chimney should be examined for cracks, loose
mortar, and other signs of deterioration and blockage.
The insert should not be installed until it is determined
that the chimney is safe for use. Since an oversized flue
contributes to the accumulation of creosote, the size of
the flue should be checked to determine that it is not too
large for the insert. The chimney should also be checked
to ensure it meets the minimum standard of the National
Fire Protection Association (NFPA) Standard 211. The
following bullets list the more critical requirements for a
properly constructed chimney:
•
The masonry wall of the chimney, if brick or modular
block, must be a minimum of 4 inches (102mm) nominal
thickness. A chimney of rubble stone must be at least
12 inches (05mm) thick.
•
The chimney must have a fire clay flue liner (or equiva-
lent) with a minimum thickness of 5/8 inch (16mm) and
must be installed with refractory mortar. An equivalent
liner must be a listed chimney liner system or other
approved material.
•
A chimney inside the house must have at least 2 inches
(51mm) of clearance to the combustible structure. A chim-
ney outside the house must have at least 1 inch (25mm)
clearance to the combustible structure. Non-combustible
fire stops must be installed at the spaces where the chim-
ney passes through floors and/or ceiling
(See Figures
7.1 and 7.2 on page 7)
.
NOTE:
In Canada, a full reline is required.
METAL HEAT CIRCULATING MASONRY
The Quadra-Fire 2700-I Insert conforms with the safety stan-
dard UL-1482 and ULC S628 (Canada) in all respects and is
approved to UL & ULC safety standards for installation and
use within a fireplace with masonry chimney, in accordance
with NFPA 211, with a direct flue collar connection
.
Figure 9.2
-
Installation Into Metal Heat Circulating Showing
Use Of Starter pipe
Listed Liner
Mantel
SEAL DAMpER AREA
Fire Risk
.
Inspection of Chimney:
• Chimney must be in good condition.
• Meets minimum standard of NFPA 211
• Factory-built chimney must be 6 inch
(152mm) UL10 HT.
WARNING
Fire Risk.
Do NOT pack insulation or other combustibles
between spacers.
• ALWAYS maintain specified clearances
around venting and spacers.
• Install spacers as specified.
Failure to keep insulation or other material away
from vent pipe may cause fire.
WARNING