114
www.qualitrolcorp.com
Starting Motor Current Value
includes the fields described below.
Average peak
value
Displays the average inrush current, over time, for the controlling cooling
motor, a value the monitor obtained during the initialization process
(learning mode). This is field is for informational purposes only.
Maximum
peak value
Displays one of the following items:
•
the maximum peak current, over time, achieved during normal
operation since the value was reset from the front panel
•
if returning from the initialization process, the maximum peak current,
over time, measured in the learning mode
This field is for informational purposes only.
Minimum
peak value
Displays one of the following items:
•
the minimum peak current, over time, achieved during normal
operation since the value was reset from the front panel
•
if returning from the initialization process, the minimum peak current,
over time, measured in the learning mode
This field is for informational purposes only.
Upper
setpoint
Allows you to enter the setpoint value that actuates the alarm relay if the
peak current, over time, equals or exceeds the value.
Lower
setpoint
Allows you to enter the setpoint value that actuates the alarm relay if the
peak current, over time, equals or falls below the value.
Actuate Alarm
(Yes / No)
Enables (Yes) / Disables (No) the alarm relay actuation if the peak
current, over time, exceeds the setpoint threshold limits.
Summary of Contents for 509ITM Series
Page 26: ...26 www qualitrolcorp com Current Input Wiring...
Page 55: ...55 www qualitrolcorp com 3 Continue with the setup procedure...
Page 101: ...101 www qualitrolcorp com...
Page 144: ...144 www qualitrolcorp com The following window will appear...
Page 167: ...167 www qualitrolcorp com The Customer Setup window displays 4 Click Load Tap Changer...
Page 178: ...178 www qualitrolcorp com Appendix...
Page 179: ......
Page 180: ......
Page 181: ......