83
www.qualitrolcorp.com
To set the Seasonal Setpoint:
1. Enter the appropriate information in the following fields:
•
Start Date:
Select the
Month
and
Day
when the Seasonal
Setpoint becomes active.
•
End Date:
Select the
Month
and
Day
when the Seasonal
Setpoint is discontinued. Normal setpoint operation resumes the
day after this date.
•
Seasonal Setpoint:
Select the temperature setpoint that will
control the relay when the Seasonal Setpoint is active.
2. Click [Load].
Ambient Temperature Forecast
includes the fields described below.
Ambient
temperature
forecast
installed
A check mark indicates that the Ambient Temperature Forecast feature is
installed. This feature only affects the setpoint in the
Control Signal 1
column of the
Controlled by Matrix
section. If the Ambient Temperature
Forecast is active and the conditions are met, the Ambient Temperature
Forecast Setpoint has priority over the Seasonal Setpoint and the
setpoint in the
Control Signal 1
column.
Forecast
function
Allows you to enable or disable this feature.
Summary of Contents for 509ITM Series
Page 26: ...26 www qualitrolcorp com Current Input Wiring...
Page 55: ...55 www qualitrolcorp com 3 Continue with the setup procedure...
Page 101: ...101 www qualitrolcorp com...
Page 144: ...144 www qualitrolcorp com The following window will appear...
Page 167: ...167 www qualitrolcorp com The Customer Setup window displays 4 Click Load Tap Changer...
Page 178: ...178 www qualitrolcorp com Appendix...
Page 179: ......
Page 180: ......
Page 181: ......