Configuration
110
www.qualitrolcorp.com
6.2.12. FR General
The user must select the reference channel for FR frequency. In addition, the user can
specify the following settings:
•
Pre-fault time between 10 ms and 10000 ms
•
Sample rate as 32, 64, 128, 256, or 512 samples per cycle
•
Post-fault time between 10 ms and 10000 ms
•
Operational limit between 100 ms and 30000 ms
•
Priority between 1 and 100
Figure 6.32 - FR General