Appendix B – INFORMA PMD-A Functions
184
www.qualitrolcorp.com
The following calculations are possible for 3U+3I+3I cabling.
Parameters
Total Nos.
Frequency 1
RMS Magnitude, fundamental
3
Phase Angle, fundamental
3
RMS Magnitude, full
3
Positive Sequence, amplitude
1
Positive Sequence, angle
1
Negative Sequence, amplitude
1
Negative Sequence, angle
1
Zero Sequence, amplitude
1
Voltage
Zero Sequence, angle
1
RMS Magnitude, fundamental
6
Phase Angle, fundamental
6
RMS Magnitude, full
6
Positive Sequence, amplitude
2
Positive Sequence, angle
2
Negative Sequence, amplitude
2
Negative Sequence, angle
2
Zero Sequence, amplitude
2
Current
Zero Sequence, angle
2
Active power, fundamental
2
Reactive Power, fundamental
2
Apparent Power, fundamental
2
Active power, full
2
Reactive Power, full
2
Power
Apparent Power, full
2
58
Summary of Contents for INFORMA PMD-A
Page 1: ...User Manual www qualitrolcorp com INFORMA PMD A Data Acquisition Unit Document ID 40 08557 01...
Page 7: ...Contents Contents iv www qualitrolcorp com References 240...
Page 8: ...About This Manual 1 www qualitrolcorp com Chapter 1 About This Manual...
Page 12: ...Overview 5 www qualitrolcorp com Chapter 2 Overview...
Page 15: ...Components and Specifications 8 www qualitrolcorp com Chapter 3 Components and Specifications...
Page 58: ...Installation 51 www qualitrolcorp com Chapter 4 Installation...
Page 86: ...Configuration 79 www qualitrolcorp com Chapter 6 Configuration...
Page 108: ...Configuration 101 www qualitrolcorp com Figure 6 22 PQ Free Interval Continuous Recording...
Page 120: ...Maintenance 113 www qualitrolcorp com Chapter 7 Maintenance...
Page 126: ...Maintenance 119 www qualitrolcorp com Figure 7 7 Voltage Calibration...
Page 166: ...Appendix B INFORMA PMD A Functions 159 www qualitrolcorp com Figure B 9 RMS Envelope PQRVC...
Page 199: ...Appendix D License Information 192 www qualitrolcorp com Appendix D License Information...
Page 246: ...References 239 www qualitrolcorp com References...