10.3 Calibrating an Expansion Pod Equipped Library
10-10
501801 Rev. 07-01-19
10.3.1 The Calibration Procedure
1.
Shut down the XLS Tape Library and switch the power switch to off.
2.
Open the LRM door.
3.
Expansion pod columns are designated A as the front column, the column closest
to the front of the library, and B as the rear column. See
4.
Make sure the XLS tape library has firmware Version 2.01.F001 PODS
SUPPORT or higher installed..
Figure 10-9
Pod calibration cartridge with the CAL label attached
Figure 10-10
Column A and B locations in an expansion pod
CAL Label
Column A
Column B
Summary of Contents for XLS-810160
Page 1: ...XLS 810160 XLS 810240 Tape Libraries Installation Manual Document No 501801 Rev 07 01 19...
Page 8: ...Table of Contents viii 501801 Rev 07 01 19...
Page 32: ...1 6 For More Information 1 24 501801 Rev 07 01 19...
Page 78: ...6 5 Installing the Rear Side Panel 6 12 501801 Rev 07 01 19 Notes...
Page 100: ...8 2 Connecting the Cables 8 8 501801 Rev 07 01 19 Notes...
Page 114: ...9 3 Logging Into X Link 9 14 501801 Rev 07 01 19 Notes...
Page 154: ...10 6 Defining Other Library Settings and Policies 10 40 501801 Rev 07 01 19 Notes...
Page 168: ...11 3 Viewing the Inventory Report 11 14 501801 Rev 07 01 19 Notes...
Page 182: ...13 3 Scanning the Inventory and Locking the Doors 13 8 501801 Rev 07 01 19 Notes...
Page 198: ...A 3 Addresses for the Media Expansion Module MEM A 8 501801 Rev 07 01 19 Notes...
Page 208: ...Index IN 6 501801 Rev 07 01 19...