Unit Dimensions - English (Cont'd)
QTC2040T
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli-
able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable
airflow patterns and possible diminished performance. The unit controls will optimize operation without nuisance high-pressure safety cut-outs;
however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is no
higher than on spring isolators. Recommended minimum clearances: Side to wall – 6'; rear to wall – 6'; control panel to end wall – 4'0'';
top – no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit.
VIEW B-B
3 15/16"
3 1/4"
6 3/4"
BOTTOM OF PANEL
7/8" TYP.
47 3/4"
46 15/16"
45 1/8"
12 5/8"
3" ANSI/AWWA
C-606 (typ)
90 1/4" BASE WIDTH
LEFT END
LIQUID OUT
25 1/4"
15 3/4"
9 7/8"
ELECTRICAL ACCESS
PANEL
LIQUID IN
LD18679
Summary of Contents for QTC2015T
Page 4: ...QUANTECH FORM QTC2 eg1 515 4 This Page Intentionally Left Blank...
Page 12: ...QUANTECH FORM QTC2 eg1 515 12 This Page Intentionally Left Blank...
Page 25: ...FORM QTC2 eg1 515 QUANTECH 25 Unit Dimensions English Cont d QTC2025T LD18674...
Page 33: ...FORM QTC2 eg1 515 QUANTECH 33 45 1 8 18 1 2 LD18682 Unit Dimensions English Cont d QTC2045T...
Page 47: ...FORM QTC2 eg1 515 QUANTECH 47 Unit Dimensions Metric Cont d QTC2045T 424 LD18702...
Page 57: ...FORM QTC2 eg1 515 QUANTECH 57 Power Wiring LD18707...
Page 58: ...QUANTECH FORM QTC2 eg1 515 58 LD18744 Power Wiring Cont d...
Page 59: ...FORM QTC2 eg1 515 QUANTECH 59 Power Wiring Cont d LD18746...
Page 60: ...QUANTECH FORM QTC2 eg1 515 60 Factory wired with optional transformer LD03611 Control Wiring...