Section 8 - Micropanel
Quantech
125
Form QTC4-NM2
Issue date: 05/12/2023
8
VSD data key
LD10605
VSD
data key
General
The VSD DATA key provides the user with displays of
VSD temperatures, voltages, currents, and other oper-
ating data. This key has multiple displays, which can
be seen by repeatedly pressing the VSD DATA or the
▲ or ▼ (Arrow) keys. An explanation of each mes
-
sage is provided.
VSD data key operation
The first VSD DATA key press displays the actual VSD
Output Frequency and Command Frequency.
VSD FREQUENCY
ACTUAL = XXX.X HZ
COMMAND = XXX.X HZ
The second key press of the VSD DATA key or the ▼
(ARROW) key displays the calculated compressor %
FLA and measured motor currents in amps for systems
1 and 2. When measuring motor current keep in mind
that measuring inverter PWM current is difficult and
meter error can be significant.
VSD COMP 1 = XXX AMPS
= XXX %FLA
COMP 2 = XXX AMPS
= XXX %FLA
The next key press displays the current limit values
set locally on the panel under the PROGRAM key, re-
motely by a BAS, and remotely by the Current Limit
input. Any current limits that are inactive will display
“XXX” instead of a numeric value.
VSD CURRENT LIMIT LOCAL = XXX %FLA
ISN = XXX
REMOTE = XXX %FLA
The next key press displays DC Bus voltage.
VSD DC BUS VOLTAGE = XXX VDC
The next key press displays the Control Panel/VSD In-
ternal Ambient Temperature and VSD Cooling Pump/
Fan Status. YYY will indicate ON or OFF.
VSD
INTERNAL AMBIENT TEMP = XXX.X °F
COOLING SYSTEM STATUS = YYY
The next key press displays the IGBT highest baseplate
temperature.
VSD IGBT BASEPLATE TEMPS
T1 = XXX °F
T2
=
XXX
°F
The next key press displays the state of the Precharge
signal, where XXX is either ON or OFF.
VSD
PRECHARGE SIGNAL = XXX
The next key press displays the setting of the VSD’s
105% FLA overload potentiometer for Compressor #1
and 2. The settings are determined by the adjustment of
the overload potentiometers on the VSD Logic Board.
These pots are factory set and do not require changing
unless the circuit board is replaced.
VSD
COMP 1 MOTOR OVERLOAD = XXX AMPS
COMP 2 MOTOR OVERLOAD = XXX AMPS
Figure 54 -
VSD data key
Summary of Contents for QTC40160
Page 22: ...Quantech 22 Form QTC4 NM2 Issue date 05 12 2023 This page is intentionally left blank...
Page 94: ...Quantech 94 Form QTC4 NM2 Issue date 05 12 2023 This page is intentionally left blank...
Page 100: ...Quantech 100 Form QTC4 NM2 Issue date 05 12 2023 This page is intentionally left blank...
Page 158: ...Quantech 158 Form QTC4 NM2 Issue date 05 12 2023 This page is intentionally left blank...
Page 187: ...Quantech 187 Form QTC4 NM2 Issue date 05 12 2023 This page is intentionally left blank...