Section 8 - Micropanel
Quantech
143
Form QTC4-NM2
Issue date: 05/12/2023
8
Unit setup mode
setting
Mode to change
Minimum
Maximum
Default
Enhanced fans
minimum fan speed
Any
0%
20%
10%
Extended leaving
chilled liquid setpoint
Any
Disabled/enabled
Disabled
****Quarterly service
warning
Free cooling is
disabled
Disabled/enabled
Enabled
****Yearly service
warning
Free cooling is
disabled
Disabled/enabled
Enabled
****3 year service
warning
Free cooling is
disabled
Disabled/enabled
Enabled
****5 Year service
warning
Free cooling is
disabled
Disabled/enabled
Enabled
****Replace oil filter
warning
Free cooling is
disabled
Disabled/enabled
Enabled
YORKTalk communica-
tion protocol type
Any
YORKTALK2 or YORKTALK3
YORKTALK 3
Table 29 -
Setup mode programmable values, cont'd
Unit setup mode messages
The following messages will be displayed for the unit
setup mode in the order they appear. The first group of
displays relates to setup parameters that relate to unit
configuration and factory set points.
The following setup display is selectable as YES or
NO using the ◄ and ► keys.
The following three setup OPTION displays are select-
able as ENABLED or DISABLED using the ◄ and ►
keys according to the options installed on the chiller:
SETUP MODE ◄DEF XXXXX LO XXXXX HI XXXXX
SYS 1 NUMBER OF COND FANS = X
SETUP MODE ◄DEF XXXXX LO XXXXX HI XXXXX
SYS 2 NUMBER OF COND FANS = X
SETUP MODE ◄DEF XXXXX LO XXXXX HI XXXXX
COMP 1 OPERATING HOURS = XXXXX
SETUP MODE ◄DEF XXXXX LO XXXXX HI XXXXX
COMP 2 OPERATING HOURS = XXXXX
SETUP MODE ◄DEF XXXXX LO XXXXX HI XXXXX
COMP 1 STARTS
XXXXX
SETUP MODE ◄DEF XXXXX LO XXXXX HI XXXXX
COMP 2 STARTS
XXXXX
SETUP MODE CLEAR HISTORY BUFFERS?
◄ ► XXXXXXXXXXXXXXXXXXXXXXXXXXXX
The following setup option is used for setting a pro-
grammable delay after change of value of a remote in-
put. The remote input is ignored until the service timer
expires.
The following setup display is selectable as STAN-
DARD or REMOTE ONLY using the ◄ and ► keys.
The following setup OPTION display allows program-
ming of the type of fan control installed. This includes
STD STAGED, OPT STAGED, OPT VSD or OPT EN-
HANCED FANS.
SETUP MODE REMOTE TEMP RESET OPTION
◄ ► XXXXXXXXXXXXXXXXXXXXXXXXXXXX
SETUP MODE REMOTE CURRENT LIMIT OPTION
◄ ► XXXXXXXXXXXXXXXXXXXXXXXXXXXX
SETUP MODE SOUND LIMIT OPTION
◄ ► XXXXXXXXXXXXXXXXXXXXXXXXXXXX
SETUP MODE ◄DEF XXXXX LO XXXXX HI XXXXX
REMOTE INPUTS SERVICE TIME = XXXX SEC
SETUP MODE RUN PERMISSIVE CONTROL
◄ ► XXXXXXXXXXXXXXXXXXXXXXXXXXXX
SETUP MODE CONDENSER FAN CONTROL
◄ ► XXXXXXXXXXXXXXXXXXXXXXXXXXXX
Summary of Contents for QTC40160
Page 22: ...Quantech 22 Form QTC4 NM2 Issue date 05 12 2023 This page is intentionally left blank...
Page 94: ...Quantech 94 Form QTC4 NM2 Issue date 05 12 2023 This page is intentionally left blank...
Page 100: ...Quantech 100 Form QTC4 NM2 Issue date 05 12 2023 This page is intentionally left blank...
Page 158: ...Quantech 158 Form QTC4 NM2 Issue date 05 12 2023 This page is intentionally left blank...
Page 187: ...Quantech 187 Form QTC4 NM2 Issue date 05 12 2023 This page is intentionally left blank...