Quantech
178
Section 9 - Maintenance
Form QTC4-NM2
Issue date: 05/12/2023
Table 35 -
Troubleshooting guide, cont'd
Problem
Possible cause
Action
System status:
Motor current limiting
A high motor current anticipatory control
has activated current limiting
Ambient temperature is high, normal
response from controller
Remote or panel limiting is in effect,
Normal response
Excess charge in system, adjust charge
Condenser coils dirty, clean condenser
Fans not operating. Check fans
VSD fault:
High baseplate temperature
Coolant level low
Add coolant
Glycol pump is defective
Replace glycol pump
VSD board is defective
Replace VSD logic board
IBGT module is defective
Check defective IGBT module
VSD cooling coil not clean
Clean VSD cooling coil
VSD fault:
Low DC Bus voltage
SCR/Diode module is defective
Check SCR/diode module
SCR trigger board is defective
Check SCR trigger board
Note:
Always remove power to the chiller and ensure the DC Bus voltage has bled off.
Summary of Contents for QTC40160
Page 22: ...Quantech 22 Form QTC4 NM2 Issue date 05 12 2023 This page is intentionally left blank...
Page 94: ...Quantech 94 Form QTC4 NM2 Issue date 05 12 2023 This page is intentionally left blank...
Page 100: ...Quantech 100 Form QTC4 NM2 Issue date 05 12 2023 This page is intentionally left blank...
Page 158: ...Quantech 158 Form QTC4 NM2 Issue date 05 12 2023 This page is intentionally left blank...
Page 187: ...Quantech 187 Form QTC4 NM2 Issue date 05 12 2023 This page is intentionally left blank...