QUANTECH
108
FORM QWC4-NM1 (221)
ISSUE DATE: 02/28/2021
SECTION 6 - OPERATION
HISTORY KEY
LD19539
HISTORY
KEY
FIGURE 52 -
HISTORY KEY
For all faults generated by the control
panel, a snapshot of all system data will
be stored immediately before shutting
down. For VSD generated faults, the VSD
captures and transmits the VSD data, and
the control panel saves the control panel
data when the VSD opens the fault relay.
To access the next FAULT HISTORY buffer number,
use the ► key; to return to the previous buffer number,
use the ◄ key.
To scroll backwards and forwards through the FAULT
HISTORY SHUTDOWN data, press the ▼ key. The
first screen will show the status of the SYSTEM. See
the example below:
SYSTEM COMPRESSOR RUNNING
The next press the ▼ key displays the ALL FAULTS
screen. The list below explains the configurations:
• ## is the FAULT HISTORY number.
• YYY is the ALL FAULT description.
• ZZ is the ALL FAULT number .
• WW is the total number of ALL FAULTS for the
current history.
To access the HISTORY FAULT or NORMAL SHUT-
DOWN information, use the following steps:
1. Press the HISTORY key to display the initial his-
tory message (above). FAULT SHUTDOWN ap-
pears under CHOOSE HISTORY TYPE.
HISTORY
CHOOSE HISTORY TYPE
◄ ►
FAULT SHUTDOWN
2. To choose NORMAL SHUTDOWNS, use the
◄
key.
HISTORY
CHOOSE HISTORY TYPE
◄ ►
NORMAL SHUTDOWN
To return to FAULT SHUTDOWN, use the ► key.
3. Press the
key. If FAULT HISTORY is selected,
the screen (below) will be displayed.
FAULT HIST ## 18-MARCH-2012 10:34:58 AM
YYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYY
The FAULT HISTORY contains data from the last 10
shutdowns, where ## is the history buffer number be-
tween one and 10, and YYYY is the fault description.
Buffer 01 gives the most recent fault information, and
10 is the oldest fault shutdown saved.
Summary of Contents for QWC4
Page 14: ...QUANTECH 14 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 64: ...QUANTECH 64 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 82: ...QUANTECH 82 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 130: ...QUANTECH 130 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 146: ...QUANTECH 146 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 152: ...QUANTECH 152 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 155: ...QUANTECH 155 NOTES...