QUANTECH
116
FORM QWC4-NM1 (221)
ISSUE DATE: 02/28/2021
SECTION 6 - OPERATION
TABLE 38 -
SETUP MODE PROGRAMMABLE
SETUP MODE VALUE
LOW LIMIT
HIGH LIMIT
DEFAULT
Compressor 1 Operating Hours
0
99999
0
Compressor 1 Starts
0
99999
0
Total Kilowatt Hours
0
99999
0
Clear History Buffers
NO
YES
—
Remote Temperature Reset
DISABLED
ENABLED
DISABLED
Remote Current Limit
DISABLED
ENABLED
DISABLED
Remote Inputs Service Time
5 min
60 min
15 min
Maximum Compressor Speed
140 Hz
203 Hz
170 Hz
Minimum Running Speed
50 Hz
100 Hz
50 Hz
System Motor Sensor To Ignore
Temp Sensor T1 / T2 / T3
None
System VI Differential Temp Setpoint (CTS)
60.0°F
33.3°C
90.0°F
50.0°C
73.0°F
40.5°C
System VI Differential Temp Setpoint (WTS)
25.0°F
13.8°C
60.0°F
33.3°C
30.0°F
16.6°C
VI Dead band (CTS and WTS)
2.0°F
1.1°C
10.0°F
5.5°C
4.0°F
2.2°C
VI Differential Temp Setpoint Offset
2.0°F
1.1°C
40.0°F
22.2°C
24.0°F
13.3°C
Minimum VSD Frequency
50 Hz
95 Hz
50 Hz
Minimum Start Frequency
50 Hz
95 Hz
50 Hz
System Low Differential Oil Pressure Setpoint
20 psid
1.37 bard
60 psid
4.14 bard
30 psid
2.07 bard
System Low Economizer Superheat
0.0°F
0.0°C
20.0°F
11.1°C
5.0°F
2.8°C
Min Oil Pump Diff Setpoint
20 psid
1.37 bard
60 psid
4.14 bard
20 psid
1.37 bard
Evaporator Pressure Cutout
24.0 psig
1.65 barg
36.0 psig
2.48 barg
25.0 psig
1.72 barg
5.0 psig
0.34 barg
36.0 psig
2.48 barg
25.0 psig
1.72 barg
High Leaving Condenser Liquid Temperature Cutout
113.0ºF
45.0ºC
159.8ºF
71.0ºC
113.0ºF
45.0ºC
Eductor Temperature Differential
5.0ºF
2.7ºC
50.0ºF
27.7ºC
15.0ºF
8.3ºC
Eductor Safety Time
1 min
1000 min
30 min
System Economizer Superheat Setpoint
8.0°F
4.4°C
50.0°F
27.8°C
13.0°F
7.2°C
Liquid Ref Injection Valve Close Threshold
5.0ºF
2.8ºC
30.0ºF
16.67ºC
10.0ºF
5.6ºC
Liquid Ref Injection Valve Open Setpoint
135.0ºF
57.2ºC
240.0ºF
115.6ºC
212.0ºF
100.0ºC
System Economizer EEV Hold Position
0.00%
50.00%
2.00%
System Economizer Max Motor Temp Setpoint
150.0ºF
65.6ºC
250.0ºF
121.1ºC
240.0ºF
115.6ºC
Economizer On Frequency
50 Hz
204 Hz
50 Hz
Economizer Off Frequency
45 Hz
203 Hz
45 Hz
High Oil Filter Differential Pressure Setpoint
10.0 psid
100.0 psid
20 psid
Summary of Contents for QWC4
Page 14: ...QUANTECH 14 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 64: ...QUANTECH 64 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 82: ...QUANTECH 82 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 130: ...QUANTECH 130 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 146: ...QUANTECH 146 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 152: ...QUANTECH 152 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 155: ...QUANTECH 155 NOTES...