QUANTECH
56
FORM QWC4-NM1 (221)
ISSUE DATE: 02/28/2021
SECTION 3 - HANDLING, STORAGE, INSTALLATION, AND REASSEMBLY
When installing relief piping there
must NOT be any piping strain.
Relief piping must be properly
aligned and supported to eliminate
any possible piping strain.
When installing relief piping an
ANSI flange or a piping union
must be used to make a
servicable piping connection.
Horizontal
Mis-aligned
Vertical
Offset
Compressed
LD16677
FIGURE 37 -
TYPICAL COMPONENTS OF RELIEF PIPING
TABLE 19 -
REFRIGERANT RELIEF CHARACTERISTICS (PER VALVE)
COMPONENT
DESIGN PRESSURE PSIG
(BAR)
AIRFLOW CAPACITY
LB/MIN (KG/S)
OUTLET CONNECTION
EVAPORATOR
235
(16.2)
55.9 (0.423)
1 in. NPTF
CONDENSER
235
(16.2)
55.9 (0.423)
1 in. NPTF
CONDENSER
(HEAT PUMP OPTION)
388
(26.8)
90.3 (0.681)
1 in. NPTF
NOTES
:
1. Dual relief valve consists of one three-way shut-off valve and two single relief valves. The valve configuration will not allow both valves to be
shut off at the same time, and valves are sized such that each relief valve has sufficient discharge capacity when used alone, which permits
safe removal of either relief valve for repair or replacement, while maintaining vessel protection.
2. Above information is for presssure vessels designed in accordancce with ASME Boiler and Pressure Vessel Code.
Summary of Contents for QWC4
Page 14: ...QUANTECH 14 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 64: ...QUANTECH 64 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 82: ...QUANTECH 82 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 130: ...QUANTECH 130 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 146: ...QUANTECH 146 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 152: ...QUANTECH 152 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 155: ...QUANTECH 155 NOTES...