SECTION 3 - HANDLING, STORAGE, INSTALLATION, AND REASSEMBLY
QUANTECH
1
New Release
INSTALLATION CHECKLIST AND REQUEST FOR AUTHORIZED START-UP TECHNICIAN
Form QWC4-CL1 (221)
The following work must be completed in accordance with installation instructions:
CUSTOMER: _________________________________
ADDRESS: __________________________________
PHONE: _____________________________________
QTC TEL NO: ___________________ QTC ORDER NO: ________________ QTC CONTRACT NO: ___________
JOB NAME: _________________________________
LOCATION: _________________________________
CUSTOMER ORDER NO: ______________________
CHILLER MODEL NO
: ____________________________
The work (as checked below) is in process and will be completed by: _____________ / ____________ /
___________
UNIT SERIAL NO
: ___________________________
Month
Day
Year
C. REFRIGERANT RELIEF PIPING (When required)
1. Refrigerant relief piping installed from unit to at-
mosphere (per local building code) .....................
D. ELECTRICAL WIRING
1. Variable Speed Drive (VSD):
a. Main power supply available ..........................
b. Wiring completed from main power supply
up to VSD.
NOTE:
DO NOT cut to length or connect to
drive without Quantech supervision ................
2. External control wiring completed according to
the wiring diagram shipped with the unit .............
3. Power available, wiring completed, and rota-
tion checked to the following drives and motors:
a. Chilled water pump(s) .....................................
b. Condenser water pump(s) ..............................
c. Cooling tower fan ............................................
NOTE:
DO NOT check compressor motor.
4. Megohm tester available for checking motor
windings. Tester not necessary unless start-up
indicates a motor winding short ..........................
5. Connect the following system inputs to their re-
spective terminals of 1TB Terminal Box: ............
a. Chilled Liquid Flow Switch -
Terminals 2 and 13 .........................................
b. Condenser Liquid Flow Switch -
Terminals 2 and 12 .........................................
c. System 1 Remote Run Permissive -
Terminals 2 and 15 .........................................
d. System 2 Remote Run Permissive -
Terminals 2 and 16 .........................................
NOTE:
If remote run permissive is not used,
place a jumper across the terminals to allow
the system to run.
e. Remote Print - Terminals 2 and 14 ................
A. QUANTECH CHILLER
1. Unit checked for shipping damage ......................
NOTE:
Any damage MUST be reported to
Quantech immediately for inspection.
Initials: __________________________________
Company Name: __________________________
Date: ____________________________________
2. Unit assembled (if shipped dismantled) and re-
frigerant piping installed ......................................
3. Vibration isolator mounted so that the unit is
level and isolators are equally deflected .............
4. If applicable, monitoring alarm is installed, func-
tional, and operational ready for service .............
B. WATER PIPING
1. Condenser water piping installed between con-
denser, pumps and cooling tower .......................
2. Chilled water piping installed between cooler,
pumps, and cooling coils .....................................
3. Make-up and fill lines installed to cooling tower
and chilled water system .....................................
4. All water piping checked for strain.
NOTE:
Piping should not spring at unit ...............
5. Water piping leak tested and flushed; water
systems filled with water and trapped air is
vented ................................................................
6. Chilled and condenser water flow available to
meet unit design requirements ............................
7. Verify the chilled and condenser liquid systems
have been connected correctly, and commis-
sioned with the correct direction of water flow.
The inlet should be at the bottom connection on
a two-pass shell. Purge air from the top of the
waterbox, using the plugged air vent, mounted
on the top of the waterbox. .................................
MODEL – QWC4
Summary of Contents for QWC4
Page 14: ...QUANTECH 14 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 64: ...QUANTECH 64 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 82: ...QUANTECH 82 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 130: ...QUANTECH 130 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 146: ...QUANTECH 146 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 152: ...QUANTECH 152 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 155: ...QUANTECH 155 NOTES...