QUANTECH
73
SECTION 4 - TECHNICAL DATA
FORM QWC4-NM1 (221)
ISSUE DATE: 02/28/2021
4
DIMENSIONS
EVAPORATOR AND CONDENSER
SHELL CODES IN (MM)
SINGLE 145/151
DUAL 136/145
B-B
C-C
D-D
M-M
N-N
A
8ˊ (2438)
10ˊ (3048)
12ˊ (3658)
12' (3658)
14' (4268)
B
6ˊ-11/16" (1846)
6ˊ-11/16" (1846)
6ˊ-11/16" (1846)
6'-3/4" (1844)
6'-3/4" (1844)
C
4ˊ-7 5/8" (1413)
4ˊ-7 5/8" (1413)
4ˊ-7 5/8" (1413)
4'-7-5/16" (1405)
4'-7-5/16" (1405)
D
2ˊ-2 15/16" (684)
2ˊ-2 15/16" (684)
2ˊ-2 15/16" (684)
2'-2-7/8" (683)
2'-2-7/8" (683)
E
2ˊ-4 11/16" (729)
2ˊ-4 11/16" (729)
2ˊ-4 11/16" (729)
2'-4-3/8" (722)
2'-4-3/8" (722)
F
1ˊ-1 15/32" (342)
1ˊ-1 15/32" (342)
1ˊ-1 15/32" (342)
1'-1-3/8" (342)
1'-1-3/8" (342)
G
1ˊ-2 11/32" (365)
1ˊ-2 11/32" (365)
1ˊ-2 11/32" (365)
1'-2-3/16" (361)
1'-2-3/16" (361)
M
6ˊ 21/32" (169)
1ˊ-6 21/32" (474)
2ˊ-6 21/32" (779)
4-3/4" (123)
10-3/4" (275)
N
1ˊ-2 17/32" (369)
2ˊ-2 17/32" (674)
3ˊ-2 17/32" (979)
5'-6" (1678)
6' (1830)
WATERBOX DIMENSIONS IN (MM)
DIM.
EVAPORATORS B, C & D
EVAPORATORS
M, N
CONDENSER B, C & D
CONDENSERS M, N
1 PASS 2 PASS 3 PASS 2-PASS 3-PASS 1 PASS 2 PASS 3 PASS 1-PASS 2-PASS 3-PASS
H
—
—
—
—
—
1ˊ-1
17/32"
(344)
1ˊ-1
17/32"
(344)
1ˊ-1
17/32"
(344)
14ˊ-1/2”
(369)
14ˊ-1/2”
(369)
14ˊ-1/2”
(369)
I
—
1ˊ-2 3/8"
(369)
1ˊ-2 3/8"
(369)
16-3/32"
(409)
16-3/32"
(409)
—
—
—
—
—
—
DIM.
REAR HEAD 2 PASS
REAR HEAD
2-PASS
REAR HEAD 2 PASS
REAR HEAD 2-PASS
J
—
6ˊ-29/32" (176)
5ˊ-3/4" (146)
K
7ˊ-21/32" (195)
6ˊ-5/32" (156)
—
ADDITIONAL OPERATING HEIGHT IN (MM)
CLEARANCE TO FLOOR
P
TYPE OF CHILLER MOUNTING
NEOPRENE PAD ISOLATORS
1-3/4” (44.5)
SPRING ISOLATORS 1”DEFLECTION
1” (25.4)
DIRECT MOUNT
3/4” (19.1)
NOTES:
1. All dimensions are approximate. Certified dimensions are available on request.
2. Evaporator and condenser water nozzles can be located on either end of unit.
3. Standard 150 psi (10.3 barg) design pressure boxes shown.
4. To determine overall height, add dimension “P” for the appropriate isolator type.
5. Front of unit is defined as side of chiller where control center is mounted.
6. In order to achieve rated performance, condenser liquid must enter the waterbox through the bottom connection for
proper operation of the sub-cooler.
7. Connected piping should allow for the removal of the compact waterboxes for tube access and cleaning.
Summary of Contents for QWC4
Page 14: ...QUANTECH 14 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 64: ...QUANTECH 64 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 82: ...QUANTECH 82 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 130: ...QUANTECH 130 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 146: ...QUANTECH 146 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 152: ...QUANTECH 152 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 155: ...QUANTECH 155 NOTES...