QUANTECH
131
FORM QWC4-NM1 (221)
ISSUE DATE: 02/28/2021
7
SECTION 7 - MAINTENANCE
GENERAL REQUIREMENTS
The maintenance requirements for QWC4 chillers are
shown below. The procedure is in the left-hand column
and the required frequency is marked with an
X
in the
right-hand column. See the notes at the bottom of the
table to maintain warranty validation.
TABLE 42 -
OPERATION/INSPECTION /MAINTENANCE REQUIREMENTS FOR QWC4 CHILLERS
PROCEDURE
DAILY
WEEKLY
MONTHLY
ANNUALLY
Record operating conditions (on applicable log form)
X
Check oil level in oil level sight glass
X
Check refrigerant levels
X
Check oil return system operation
X
Check operation of motor starter
X
Check oil heater operation
X
Check 3-phase voltage and current balance
X
Check programmable operating setpoints and safety
cutouts. Make sure they are correct for the application.
X
Verify condenser and evaporator liquid flows
X
Check and repair leaks as needed¹
X
Check and tighten all electrical connections
X
Check
the motor windings resistance
X
Clean or back flush VSD heat exchanger
X
¹
Replace VSD coolant (after cleaning heat exchanger)
X
Perform oil analysis on compressor lube oil
X
¹
Perform refrigerant analysis
X
Perform Eddy current testing and inspect tubes
X²
Clean evaporator and condenser tubes
X²
For operating and maintenance requirements listed above, refer to appropriate service literature, or contact a local Quantech Field Service
Office.
¹ This procedure must be performed at the specified time interval by an industry certified technician, who has been trained and qualified
to work on this type of Quantech equipment. A record of this procedure being successfully carried out must be maintained on file by the
equipment owner should proof of adequate maintenance be required at a later date for warranty validation purposes.
² More frequent service may be required, depending on local operating conditions or relaxed with good engineering controls (water quality).
Compressor vibration analysis is not prescribed. Due
to the compressor design, a typical vibration analysis
can be misleading.
Avoid periodic oil filter changes. Change the oil, filter,
and filter driers only when an oil analysis indicates a
moisture issue.
Summary of Contents for QWC4
Page 14: ...QUANTECH 14 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 64: ...QUANTECH 64 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 82: ...QUANTECH 82 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 130: ...QUANTECH 130 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 146: ...QUANTECH 146 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 152: ...QUANTECH 152 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 155: ...QUANTECH 155 NOTES...