Variable Speed Drive
The VSD is removed, and prepared for shipping sepa-
rately.
• All wiring harnesses are coiled and secured.
• Cooling hoses are removed.
• Hardware is added to the package with the miscel-
laneous nuts, bolts and fittings.
Discharge Isolation Valves
If equipped, the discharge isolation valves are removed
and shipped loose.
Miscellaneous Items
The following items are shipped together:
• Four vibration isolation pads (or optional spring
isolators and brackets)
• VSD inhibitor
• Other shipped loose items, including piping, wa-
ter temperature controls, wiring, etc.
INSPECTION, DAMAGE, AND SHORTAGE
Inspection
Check each unit on arrival to ensure all major compo-
nents, boxes and crates are received, undamaged, and
compared to the packing list.
Damage
Before unloading, inspect each unit for any visible
signs of damage while still on the trailer or rail car.
Report any damage or signs of possible damage to the
transportation company immediately for the compa-
ny's inspection.
Quantech will not be responsible for any
damage or loss of parts in shipment or
at job site.
Shortage
After inspecting the assemblies, all containers should
be opened and contents checked against the packing
list. Any material shortage should be reported to Quan-
tech immediately. Refer to
Shipping Damage Claims
(Form 50.15-NM
).
Storage
Units are shipped without export crating unless crat-
ing has been specified on the sales order. Observe the
following precautions, if the unit is to be stored before
installation:
If the temperature is outside of the 40°F
to 110°F (4°C to 43°C) range, make sure
the waterboxes and VSD heat exchanger
are completely drained of all liquid, which
could freeze. Make sure the condenser
and evaporator tubes are completely dry.
The VSD coolant must be drained and
replaced with anti-freeze solution.
• The chiller must be blocked under the end sheets.
• Ensure that all openings, such as water connec-
tions, are securely capped.
• Store the unit in a location where:
• It will NOT be exposed to ambient air tem-
peratures exceeding 110°F (43°C).
• There is minimal activity to limit the risk of
accidental physical damage.
• It is protected from rain or mist. Cover with a
tarp, if the unit will be located outside.
• If the unit is stored longer than six months, follow
the requirements from
Long-Term Storage Peri-
odic Checklist and Logs for QWC4 Screw Chillers
(
Form 50.20-NM9
).
• Inspect the unit periodically during storage.
• To prevent inadvertent operation of the pressure
relief devices, the unit must not be steam cleaned.
Summary of Contents for QWC4
Page 14: ...QUANTECH 14 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 64: ...QUANTECH 64 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 82: ...QUANTECH 82 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 130: ...QUANTECH 130 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 146: ...QUANTECH 146 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 152: ...QUANTECH 152 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 155: ...QUANTECH 155 NOTES...