SECTION 3 - HANDLING, STORAGE, INSTALLATION, AND REASSEMBLY
the panel end only, and run in water tight conduit. Run
shielded cable separately from mains cable to avoid
electrical noise pick-up. Use the control panel cable
entry to avoid the power cables.
Voltage-Free Contacts
Voltage-free contacts connected to the panel must be
suitable for 115 VAC 10 mA, for example, gold con-
tacts. If the voltage-free contacts form part of a relay or
contactor, the coil of the device must be suppressed us-
ing a standard R/C suppressor such as P/N 031-00808-
000. The above precautions must be taken to avoid elec-
trical noise, which could cause a malfunction or damage
to the unit and its controls.
Chilled Liquid and Condenser Pump Starter
Terminals 23 and 24 on 1TB close to start the chilled
liquid and/or condenser water pumps. This contact can
be used as a master start/stop for the pumps in conjunc-
tion with the daily start/stop schedule.
Run Contact
Terminals 21 and 22 on 1TB close to indicate that a
system is running.
Alarm Contacts
The system has a single voltage-free contact, which
will operate to signal an alarm condition whenever any
system locks out, or there is a power failure. To obtain
the system alarm signal, connect the alarm circuit to
voltage-free Terminals 25 and 26.
SYSTEM INPUTS
The circuitry for the following system inputs is a 115
VAC circuit. Contacts must be gold and rated for low
current (5 mA). Connect the switches per instructions
below. See
for the terminal con-
nections.
Chilled Liquid Flow Switch
Connect this switch between Terminals 2 and 13 of
1TB to provide protection against loss of liquid flow,
which will cause evaporator freeze-up, if the chiller is
permitted to run.
Condenser Liquid Flow Switch
This switch is expected across Terminals 2 and 12 of
1TB to indicate loss of liquid flow, which can result in
a rapid high head transient on the chiller.
Remote Run Permissive
A remote run permissive input is available and requires
a dry contact to start and stop. Remote dry contacts are
connected between Terminals 2 and 15 of 1TB. If re-
mote run permissive is not used, place a jumper across
the terminals to allow the system to run.
Remote Print
Closure of suitable contacts connected to Terminals 2
and 14 of 1TB will cause a hard copy of Operating
Data/Fault History to be printed, if an optional serial
printer is connected to the RS-232 port.
Optional Heat Pump Remote Mode Selection
A remote mode selection input is available when the
chiller is purchased with heat pump option. If the op-
tion is enabled and remote mode selection is required,
connect a switch across Terminals 10 and 41 of 1TB
to switch between chiller and heat pump operation re-
motely.
• Contacts Open = Chiller Mode
• Contacts Closed = Heat Pump Mode
TABLE 20 -
SYSTEM INPUT CONNECTIONS
INPUT
1TB TERMINALS
Chilled Liquid Flow Switch
2 and 13
Condenser Liquid Flow Switch
2 and 12
Remote Run Permissive
2 and 15
Remote Print
2 and 14
Remote Heat Pump Mode
10 and 41
Optional Remote Setpoint Offset
The control panel provides for external input to reset:
• Compressor current limits
• Liquid temperature setpoints for Leaving Chilled
Liquid, and Heat Pump Leaving Condenser Liquid.
ANALOG INPUTS
The circuitry for the following analog inputs is for 10
VDC or 20 mA current inputs when remote setpoint
control options are purchased and enabled.
Leaving Chilled Liquid Temperature Reset
Control
Install input for Leaving Chilled Liquid Temperature
Control remote reset across Terminals 17 (+) and 18 (-)
of the 1TB Terminal Block.
Summary of Contents for QWC4
Page 14: ...QUANTECH 14 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 64: ...QUANTECH 64 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 82: ...QUANTECH 82 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 130: ...QUANTECH 130 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 146: ...QUANTECH 146 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 152: ...QUANTECH 152 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 155: ...QUANTECH 155 NOTES...