QUANTECH
88
FORM QWC4-NM1 (221)
ISSUE DATE: 02/28/2021
SECTION 6 - OPERATION
values are exceeded, the minimum or maximum
value will be used.
•
Remote Current Limit Analog Reset:
Set the
CURRENT LIMIT setpoint via the REMOTE
CURRENT LIMIT analog input. A zero signal
input (0% ) equates to the maximum current limit
setpoint as defined under the PROGRAM key
CURRENT LIMIT setpoint. A full scale sig-
nal input (100% input) equates to the minimum
current limit setpoint as defined under the PRO
-
GRAM key CURRENT LIMIT setpoint. The
current limit value is linear and may be adjusted
anywhere between the maximum and minimum
points of 0% (no offset) and 100% (max. current
limiting).
This input may be used in LOCAL or REMOTE
CONTROL MODE. This input will be ignored
if the REMOTE CURRENT LIMIT is disabled
under the OPTIONS key. Once a change to the
input is registered, a timer is set to the value of
the REMOTE INPUTS SERVICE TIME as
programmable under the UNIT SETUP MODE
at the factory for the default value of 15 minutes.
The low limit is five minutes, and the high limit
is 60 minutes.
The remote input will be ignored until this timer
expires. The timer assures that rapid changes in
a remote reset signal don’t result in poor tem-
perature control or excessive compressor cycling.
In most instances, this timer will not need to be
changed, since reset more often than 15 minutes
will create problems with chilled liquid tempera-
ture control. Contact a Quantech Factory Service
Center if a timer change is required.
USER INTERFACE
The keys, detailed in the following pages, provide vari-
ous displays of unit related data. Press the▲ or ▼ key
repeatedly to select multiple display messages. The
display messages that contain a number symbol (#)
will be replaced with the chiller's present value, which
are listed below:
• ###.# °F = Temperature Data
• ####.# % = Percent (0% to 100%)
• ### = :
• Time Data, i.e. seconds (SEC)
• PSIG/PSID = Pressure Gauge/
Pressure Difference
• Hz = Hertz
• AMPS = Amperage
• FLA = Full Load Amperage
Summary of Contents for QWC4
Page 14: ...QUANTECH 14 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 64: ...QUANTECH 64 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 82: ...QUANTECH 82 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 130: ...QUANTECH 130 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 146: ...QUANTECH 146 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 152: ...QUANTECH 152 FORM QWC4 NM1 221 ISSUE DATE 02 28 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Page 155: ...QUANTECH 155 NOTES...