27
CANopen
HBM
QuantumX
Analog input operating mode
Object description
Index
6112 (hex)
24850 (dec)
Note
Object name
AI_Operating_mode
A value other than 0 sets the analog input
channel to special operating modes
Object code
Array
channel to special operating modes.
Data type
UINT8
CiA standard
Yes
Category
Optional
Value description
Sub-index
0 (hex)
1 (hex)
2 (hex)
to
C7 (hex)
Description
Number of entries
AI_Operating_
mode 1
AI_Operating_
mode 2
AI_Operating_mode
199
Entry category
Mandatory
Mandatory
Optional
Optional
Access
ro
rw
rw
rw
PDO mapping
No
No
No
No
Value range
1
−
199
UINT8
UINT8
UINT8
Default value
No
0
0
0
Value
Description
0
Channel off (not operating)
1
Normal operation
2
−
9
Reserved
10
−
255
Implementation specific
Several signals
QuantumX modules are able to deliver several signals from one connector.
Module MX410:
1. Signal S1 with filter setting 1
2. Signal S2 with filter setting 2
For these signals, all the objects described above are available.
Peak unit MX410: 8 signals
1. Peak 1 with different modes, (positive peak, negative peak, peak-to-peak)
2. Peak 2 with different modes, (positive peak, negative peak, peak-to-peak)
.
.
.
8. Peak 8 with different modes, (positive peak, negative peak, peak-to-peak)
For these signals, all the objects in the analog input function block described above are
read-only.