37
CANopen
HBM
QuantumX
Input scaling 2 field value (physical output, float format, point 2)
Object description
Index
x122 (hex)
24866 (dec)
Note
Object name
Input_scaling_2_FV
This object defines the field value of the
second calibration point for the analog input
Object code
Array
second calibration point for the analog input
channel. It is scaled in the physical unit of
Data type
Float, INT16, INT24, INT32
channel. It is scaled in the physical unit of
the field value.
CiA standard
Yes
Category
Optional
Value description
Sub
-
index
0 (hex)
1 (hex)
2 (hex)
to
C7 (hex)
Description
Number of entries
Input scaling 2
Field value 1
Input scaling 2
Field value 2
Input scaling 2
Field value 199
Entry category
Mandatory
Mandatory
Optional
Optional
Access
ro
rw
rw
rw
PDO mapping
No
No
No
No
Value range
1
−
254
Data type specific
Default value
No
No
No
No
Input scaling 2 process value (electrical input, float format, point 2)
Object description
Index
x123 (hex)
24867 (dec)
Note
Object name
Input_scaling_2_PV
This object defines the process value of the
second calibration point for the analog input
Object code
Array
second calibration point for the analog input
channel. It is scaled in the physical unit of
Data type
Float, INT16, INT24, INT32
channel. It is scaled in the physical unit of
the process value.
CiA standard
Yes
Category
Optional
Value description
Sub
-
index
0 (hex)
1 (hex)
2 (hex)
to
C7 (hex)
Description
Number of entries
Input scaling 2
Process value 1
Input scaling 2
Process value 2
Input scaling 2
Process value 199
Entry category
Mandatory
Mandatory
Optional
Optional
Access
ro
rw
rw
rw
PDO mapping
No
No
No
No
Value range
1
−
254
Data type specific
Data type specific
Data type specific
Default value
No
No
No
No