background image

Owners Manual 

Quantum Energy Technologies

 

 

6m.1: Trouble Shooting Chart 

PROBLEM 

POSSIBLE CAUSES 

POSSIBLE CORRECTIVE STEPS 

COMPRESSOR 
WILL NOT RUN 
 

1.  Main switch open 
2.  Fuse blown, breakers open 
 
 
3.  Thermal overloads tripped 
4.  Defective contactor or coil 
5.  System off by protection device 
6.  No heating required 
7.  Liquid line solenoid will not open 
8.  Motor electrical problem 
9.  Loose wiring, faulty controller sensor 

/ broken wire 

10. Compressor  failure 

1. Close 

switch 

2. Check 

electrical 

circuits and motor windings for shorts. 

Check for overloads and loose connections.  Replace 
fuse or reset breaker. 

3. 

Check unit when back on line, auto reset 

4. Repair 

or 

replace 

5. 

Determine cause and correct 

6. 

None, should start on call for heating 

7. 

Repair or replace coil 

8. 

Check motor for open or short circuit, or burnout 

9. 

Check all wire junctions. Tighten all terminals 

 
10. Replace compressor 

COMPRESSOR 
NOISY OR 
VIBRATING 

1.  Refrigerant flooding compressor 
2. Refrigerant overcharged 
3.  Improper line support 
4. Worn compressor 

1. 

Check expansion valve setting and superheat 

2. Remove 

excess 

refrigerant 

3. 

Relocate or add supports 

4. Replace 

compressor 

EVAPORATOR COIL 
ICING UP  

1.  Lack of refrigerant 
2.  Restricted air or cold air re-circulated
3.  Expansion valve not opened 

sufficiently 

4.  Expansion valve power element 

leaks 

5.  De-ice interval too long for that 

particular site 

6.  Too much cold water to be heated 

1. 

Check for leaks. Repair and replace refrigerant. 

2. 

Proper clearance for air flow 

3. 

Check and adjust for proper superheat 

 
4. 

Replace expansion valve 

 
5. 

Shorten the de-ice interval 

 
6. 

Reduce the amount of water or add a head pressure 
regulator to the machine 

1.  Compressor loses oil owing to 

refrigerant flooding back 

2.  Compressor loses oil owing to 

refrigerant leaks 

3.  System contaminated, and/or Liquid 

injection capillary tube blocked 

4.  Suction superheat too high 
5.  Oil degrades owing to high 

temperature 

COMPRESSOR 
THERMAL SWITCH 
OPEN 

 
6.  De-icing could not de-ice completely. 
7.  Crankcase heater burned out 

1. 

Check and fix the flood back problem. Add oil if 
necessary 

2. 

Find and repair the leakage. Add oil if necessary 

 
3. 

Purging the system and change oil and the filter/drier 

 
4. Adjust 

superheat 

5. 

Find and rectify the high discharge temperature. Change 
the oil (to the requirement amount!) purge the system 
and change the filter/drier 

6. 

Find and rectify the de-ice problem 

7. 

Replace crankcase heater 

HIGH 
DISCHARGE 
PRESSURE 

1.  Non condensibles in system 
2. Refrigerant overcharged 

1. 

Remove with authorized procedures 

2. Remove 

excess 

charge 

3.  Water temp cut-out setting too high 

3. 

Check the settings 

4.  Condenser water tube scaled 

4. 

Clean the tube 

5. Blocked condenser 

5. Clean 

condenser 

6.  Higher suction pressure than normal 

6. 

Refer to ‘High Suction Pressure’ 

1.  Lack of refrigerant 

1. 

Check for leaks. Repair then replace refrigerant. 

2. Evaporator dirty 

2. Clean 

evaporator 

3.  Clogged filter drier (pipe after the 

filter cold) 

3. 

Replace filter drier 

LOW SUCTION 

 

PRESSURE 

4.  Expansion valve malfunctioning 

(leakage phial/bulb) 

4. 

Check and change it 

 

5.  De-icing could not de-ice completely 

5. 

Check and adjust the de-icing setting if necessary. 

UNSTABLE 
SUCTION 

1. Expansive valve hunting 

1. 

Check and close the valve for proper superheat 

2.  Ice-blocking in the expansion valve 

(ice up in the Valve body) 

2. 

Check and change the refrigerant and the drier 

PRESSURE 
UNSTABLE 
DISCHARGE 

1.  Non condensibles in system 

1. 

Remove with authorized procedures  

2. Refrigerant overcharged 

2. Remove 

excess 

charge 

PRESSURE 
COMPRESSOR 
INTERVAL TOO 
SHORT 

1. Erratic water thermostat 

1. Replace 

sensor 

2.  Insufficient water flow 

2. Adjust 

flow 

1.  Low voltage during high loads 

1. 

Check supply voltage 

MOTOR 

2.  Defective or grounded motor wiring 

2. Replace 

compressor 

OVERLOAD 

3. Loose power wiring 

3. 

Check all connections and tighten 

RELAYS OPEN 

4.  High evaporating temperature 

4. 

See steps for high discharge 

OR BLOWN 

5.  Liquid refrigerant flood back 

5. 

Too much refrigerant. Check the evaporator, the fan and 
the TX valve opening. 

FUSES 

6. Unbalanced voltage 

6. 

Check voltage. Contact Power Company 

 
 

Document Number : QDC0049PD-5 

 

Page 29 of 33

 

Summary of Contents for 67ACW2-134

Page 1: ...MANUAL Including Installation Instructions and Warranty Information To Suit 67AC HEAT PUMP WATER POOL FLOOR HEATERS MODELS 67ACW2 134 67ACW2 134 C 67ACW 134 67ACW 134 C 67ACW 417 67ACW 417B 67ACP2 22...

Page 2: ...TION 9 3a Handling 9 3b Location 10 3b 1 Unit Placement 10 3b 2 Service Access 10 3b 3 Clearances 11 3b 4 Sound Isolation 11 3b 5 Vibration Isolation 11 3b 6 Damper for Centrifugal Fan Models 11 3c Re...

Page 3: ...ttons 20 4b 3 SET Button 20 4b 4 UP Button 20 4b 5 Down Button 20 4b 6 Programming Menu 20 4b 7 Adjusting 20 4b 8 Operating Principle 21 4b 9 Fault Codes 21 Section 5 OPERATION 22 5a Pre Start Up 22 5...

Page 4: ...vered By Warranty 31 7c Before Phoning For Service 31 List of Figures Figure 1 Suggested Pushing Arrangement 9 Figure 2 Suggested Lifting Arrangement 9 Figure 3 Clearance Requirements 10 Figure 4 Typi...

Page 5: ...tate Territory Postcode Date of Purchase Purchased From Model Serial Number Date of Manufacture Details on Data Plate on water heater 1b Installer s Details Date of Installation Installer s Name Addre...

Page 6: ...ture reservoir It has a cold side to absorb heat at low temperatures and a hot side to deliver heat at high temperatures The Quantum system has an air coil as the cold side of the refrigeration circui...

Page 7: ...sical damage after the unit leaves the factory For unit shipping weights see section 2d 1 Physical Data Table 2d Physical Data 2d 1 Physical Data Table PHYSICAL DATA 67ACW2 134 67ACW2 134 C 67ACW 134...

Page 8: ...OFF POWER BEFORE OPENING COVER 1225 360 210 1121 1425 1175 920 1121 Model No67A CW2 134 C Serial No SUZ0027 Date of MfgDec 2006 Hot Water Generating Rate542 l h Heating Capacity22 10 kW Power Input t...

Page 9: ...the unit Do not push or pull the unit by anything other than the base Block the pushing vehicle away from the unit to prevent damage to the sheet metal cabinet and end frame see Figure 1 To lift the...

Page 10: ...cated wind deflectors 3b 2 Service Access Each end of the unit must be accessible after installation for periodic service Compressor filter drier and liquid line solenoid valve are accessible from the...

Page 11: ...necessary locate the unit away from sound sensitive areas Avoid locations beneath windows or between structures where normal operating sounds may be objectionable Reduce structurally transmitted sound...

Page 12: ...and pressure indicators located close to the unit to aid in unit servicing 7 A strainer or other means of removing foreign matter from the water before it enters the pump Place the strainer far enoug...

Page 13: ...ated As a guide the following parameters should be used Calcium Hardness 70 150 mg L 3e 3 Pool Heater Applications It is imperative that the correct chemical balance be maintained in your pool and or...

Page 14: ...owever if desired an external by pass can be plumbed in for use if the heater is disconnected or to isolate it from the hydraulic circuit In this way water would still flow but not through the heater...

Page 15: ...the heating system The Schematic of the heating system is shown in Fig 6 Figure 6 The Schematic of the heating system Expansion Tank NOTES 1 There must be a proper expansion tank in the system and the...

Page 16: ...11 111 Locked Rotor Amps LRA Fan 6 5 24 6 5 NOTES 1 Voltage within 10 of nameplate rating 2 Phase imbalance within 3 3 Single conductors should be used for power connections 4 Single point disconnect...

Page 17: ...R N 16 L1 L1 L3 L2 QF1 FR1 0 48 L N QUANTUM ELECTRONICCONTROL Air De ice Comp Water LP HP Neutral YV YV KM1 N ST1 EH DIV LIV COMP FAN 1 2 3 4 5 7 11 12 13 ST2 ST3 ST4 14 Comp Fanand LP HPProtection 1...

Page 18: ...R2 L N QUANTUM ELECTRONIC CONTROL Air De ice Comp Water L P H P Neutral Y V K M 1 N S T 1 E H D I V L I V C O M P F A N 1 2 3 4 5 7 1 2 1 3 S T 2 S T 3 ST4 1 4 Comp Fan and LP HP Protection 1 0 W P K...

Page 19: ...nents on the Left and Front Panel UP Figure 9 Control Components In The Enclosure 4b Control Operation 4b 1 User Adjustable Parameters The sophisticated Digital Controller allows the 67AC series heat...

Page 20: ...ture c During the time delay start period press hold for 3 seconds to force a compressor start When the compressor is running press hold for 3 seconds to force a compressor shutdown 4b 5 DOWN Button a...

Page 21: ...ower than the ambient temperature and this temperature difference lasts for 5min de icing is activated During the de icing time the fan stops When the evaporator temperature rises to 8 C 2nd Level F08...

Page 22: ...nd start the hot water pump Check all piping for leaks and vent the air from the condenser as well as from the system plumbing for a building heater 5b Commissioning 1 If the controller calls for heat...

Page 23: ...the flow switch will close once satisfactory flow rate is achieved If the hot water temperature is below the stage on temperature and all equipment protection devices are closed the unit will start Th...

Page 24: ...or its duly appointed and authorised representative who will arrange for a service technician to check and or repair the machine 5e Equipment Protection Alarms not available for all models The followi...

Page 25: ...ble to advise if the noise being produced is abnormal 6b 3 Frost on Sump No frost should be present on the sump of the compressor 6c Refrigerant Sight Glass Observe the refrigerant sight glass weekly...

Page 26: ...ally required except the occasional removal of dirt and debris from the outside surface of the fins Clean as often as necessary to keep the coil free from foreign matter For cleaning use locally purch...

Page 27: ...problem can be traced to the power element only unscrew the element from the valve body without removing the valve but only after pumping the unit down WARNING Disconnect and tag out all power source...

Page 28: ...ould be wired to open whenever the liquid line solenoid valve is energized This can be accomplished by wiring the hot gas solenoid in parallel with the liquid line solenoid The pressure control is fac...

Page 29: ...ould not de ice completely 7 Crankcase heater burned out 1 Check and fix the flood back problem Add oil if necessary 2 Find and repair the leakage Add oil if necessary 3 Purging the system and change...

Page 30: ...such defect NOTE Corrosion of the heat exchanger is caused by improper water quality PH balance Corrosion of this nature will void all warranties THE WARRANTY SHALL NOT APPLY IN ANY OF THE FOLLOWING...

Page 31: ...irements Relocation of equipment due to complaints of noise level or inappropriate location No responsibility shall be accepted for damage to the system or property if it is found that continued use o...

Page 32: ...Owners Manual Quantum Energy Technologies Customer Notes Document Number QDC0049PD 5 Page 32 of 33...

Page 33: ...ALIA A B N 88 095 959 327 Phone 61 2 9699 7444 Fax 61 2 9699 5386 NOTE While every care has been taken to ensure the accuracy in preparing this publication No liability can be accepted for any consequ...

Reviews: