Choosing a Location
Quantum DXi4700 Installation Guide
6
Table 2:
DXi4700 G2 Rack Requirements
DXi4700 G2 Node
DXi4700 G2 Expansion Module
(JBOD)
Height
2U, 3.4 inches (8.7 cm)
3.4 inches (8.7 cm)
Width (side to side)
17.5 inches (44.4 cm)
17.6 inches (44.6 cm)
Depth (front to back)
28.6 Inches (72.6 cm)
23.7 inches (60.2 cm)
Weight (stand alone)
49.4 pounds (22.4 kg)
59.2 pounds (26.8 kg)
Rack Space Required
2U
2U
Air clearance
Open 4 in (10.2 cm) behind unit for proper air flow
Environmental Conditions
The installation site must have the following environmental conditions:
Humidity:
l
DXi4700 G1 - 20% to 80% (non-condensing) with a maximum humidity gradient of 10% per hour
l
DXi4700 G2 - 10% to 80% (non-condensing) with a maximum humidity gradient of 10% per hour
Temperature:
l
DXi4700 G1 - 10° to 35°C (50° to 95°F) with a maximum temperature gradient of 10°C per hour
l
DXi4700 G2 - 10° to 35°C (50° to 95°F) with a maximum temperature gradient of 20°C per hour
Altitude:
l
DXi47001 G1 – 16m to 3048 m (–50 to 10,000 ft)
l
DXi47001 G2 – 16m to 3048 m (–50 to 10,000 ft)
These environmental conditions apply when the DXi4700 system is in operation. For additional
specifications, refer to the
DXi4700 Site Planning Guide
.