3.4 Rename and register the control terminals
On ‘Setup’->’Device’, operator can always give each location/control terminal a meaningful
name by inputting the new name over ‘Device x’ in the centre such as ‘Garage’,
‘Fridge1’ ,’Office’ etc. This designation can be changed at any time by the same process.
The operator will need to access ‘Setup’->’Device’ page to register/pair a new control terminal
before using it. More details on how to do this can be found in Chapter 2.2.
3.5 Temperature/humidity setting within the APP
Operators can set the upper limit (maximum value) and lower limit (minimum value) for the
controlled zones via the control panel, so that the related relay can be triggered on or off once
the measured temperature/humidity has reached the set point. The upper temperature needs
to be at least 1°C higher than the bottom temperature to avoid hysteresis issues. For the
same reason, the upper humidity should be at least 3% higher than the bottom value.
Figure 14 Temperature/humidity control setting
The setting controls are in ‘Setup’ -> ‘Sensor’ -> ‘Name of terminal’. There are four controls
per relay, two for temperature on/off and the same for humidity. Enter each parameter and
then save before moving on to the next. A successful entry will generate a message at the
bottom of the page (close the keyboard to see it). Press setup to go back one page, to set the
next relay.