Section 3: Setup Mode

Page 6

PM9605 Revision 1, 9605 Version 36.1.1

The 9605's Setup mode allows the user to configure the unit for a particular application.  The Setup mode is used
to setup the following variables before attempting to communicate with the PLC.  

<

  9605 node address 

<

  SLC-500 (DH+) node address 

<

  Watchdog file number

<

  Watchdog element number 

<

  Dialogue File number

<

  Operating Mode A or Mode B

The Setup mode is activated when the 9605 is powered up with the slide switch (located on the side of the 9605)
is in the on position.  This condition is only tested on power up, or when restarting the 9605 during the display of 
an error code.

The Setup mode will prompt the user to enter the parameters mentioned above.  The information that is entered
will be saved in nonvolatile memory (EEPROM).  This means that the user only has to configure the 9605 once
(the Setup data will be maintained even if power is removed), but you can change the configuration as often as
you need to.

The slide switch on the side of the unit actually controls the write enable line to the EEPROM.  So when the switch
is in the on position the EEPROM can be changed;  when in the off position the EEPROM cannot be changed. 
With this in mind the slide switch should be kept off whenever the 9605 is not in Setup mode.  This will assure that
the 9605's setup data is safe.  

Slide switch down toward the bottom of the 9605 = ON

Slide switch up toward the top of the 9605 = OFF

3.1  Using the Setup Mode

Upon entry into the Setup mode, the LEDs will be all Red, then one-by-one the LED's will turn green.
Immediately they will turn off with the exception of the setting of the Operating Mode LED.  This distinctive display
pattern will act to confirm the Setup mode selection.

Once the Setup mode has been selected, the 9605 will use its LEDs to indicate the current values of the several
parameters, and you may use its switches to change the values.  The switches are defined as follows:

1

9605's node address

2

SLC-500's (DH+) node address

3

Watchdog File number

4

Watchdog element number

5

Dialogue File number

6

Operating Mode : Red = Mode A,  Green = Mode B.

7

Restart 9605: This button will "Warm boot" the 9605 in order to re-establish  communications with the

processor.  This key  is only active when the 9605 is in Setup mode or when the 9605 is displaying an
error code.  It will prevent the user from cycling power to the 9605 when the setup process is complete
or to restart the 9605 when in error.  

8

Enter Test Diagnostic Mode (Refer to section 3.2 for more information)

Summary of Contents for 9605

Page 1: ...ll QUARTECH CORPORATION be responsible or liable for any damage including indirect or consequential losses resulting from the use misuse or application of the unit The text illustrations charts and ex...

Page 2: ...Image bits Mode B 3 2 3 Switch Image bits Mode A 3 2 4 Green Amber Red LED bits Mode A only 4 2 5 Switch Configure Bits 4 2 6 Watchdog Timer Option 5 Section 3 Setup Mode 6 3 1 Using the Setup Mode 6...

Page 3: ...nication interface modules or Input Output modules to operate The 9605 connects directly to the SLC 500 s DH port When the 9605 is powered up the LEDs will imediately display a version number before i...

Page 4: ...an 99 For example a valid Dialogue File would be B 10 The Dialogue File must be at least 2 elements 0 and 1 for operating Mode B or at least 5 elements 0 thru 4 for operating Mode A If these elements...

Page 5: ...ad the status of the switch image bits from the SLC 500 then if the switch is pressed it will compliment the state of the associated register bit For example if the register bit is energized and the s...

Page 6: ...ergized For example to light LED 10 red bit number 09 of the red register must be energized A priority scheme exists so that if more than one color register bit is energized for the same LED the outco...

Page 7: ...ering the file number and the element number during the setup of the 9605 see section 3 The 9605 will write a value of zero 0 to the accumulator of this timer on a regular and continuous basis therefo...

Page 8: ...on the EEPROM cannot be changed With this in mind the slide switch should be kept off whenever the 9605 is not in Setup mode This will assure that the 9605 s setup data is safe Slide switch down towar...

Page 9: ...one 1 You may press as many keys as needed to make up the desired number For the example to make the Dialogue File 24 LEDs 11 and 14 need to be switched Red the rest of the LEDs should be green Once...

Page 10: ...ent each individual digit of the decimal number The table to the left shows the possible combinations for a one digit decimal number The bits of the BCD number sum to equal the decimal digit if each b...

Page 11: ...nate upon pressing a particular key If the LED does not illuminate with the action of the switch the keyboard may be damaged 2 LED test This test will prove that power is reaching all of the printed c...

Page 12: ...ct between multiple SLC 500 s that may be on the network The physical connection between the 9605 and SLC 500 processor is through the Three position terminal block The 9605 provides both a nine pin D...

Page 13: ...cted at each end of the trunkline to provide proper line loading thus reducing signal interference Devices intended for use on the DH network must include as part of their interface hardware a line te...

Page 14: ...isy power supply voltage Slide switch was left in the on position It should only be on during Setup Mode 15 EEPROM write disabled Slide switch is not in the on position 21 No activity on the network C...

Page 15: ...t a timer file Not enough WD file elements The WD File entered during setup does not exist in the PLC or it is not a timer file The timer file may not be large enough to contain the element selected d...

Page 16: ...pplications Environment Operating Temperature 0 c to 60 c Storage Temperature 20 c to 70 c Operating Humidity 0 to 95 non condensing Storage Humidity 0 to 95 non condensing Vibration 10Hz to 55Hz Disp...

Page 17: ...rsof type 12 cpi The strip measures 4 x 0 7 inches 0 01 inch max thickness Quartech can provide custom legends produced to your specifications Custom graphics and color may be included in each legend...

Page 18: ......

Reviews: