Section 3: Setup Mode

Page 7

PM9605 Revision 1, 9605 Version 36.1.1

The last two rows of LEDs will be used to display the current value of the 9605 node address, SLC-500 (DH+)
node address, Watchdog file number, Watchdog element number, or Dialogue File number depending on which
parameter is selected.  The value will be entered and displayed as a two digit BCD number (See figure 1).  

Example

Perhaps the best way to describe the process of changing the Setup parameters is with an example:  To set the
Dialogue File to B 24, the operator would:

<

Position the slide switch to the on position.  Then apply the power to the 9605, to enter Setup Mode.  If
Setup mode is entered properly the 9605 will cycle every LED green followed by the indicators turning off
with the exception of the Operating Mode LED.

<

After power up, press the [5] key (see page 7 for key assignments).  Notice how the number 5 led turns
Amber and the last two rows of LEDs change; The last two rows of LEDs display the current value of the
parameter.  The value is a two digit BCD number.  (See page 10 for a review of BCD numbers.)

<

When LED 5 is amber, the Dialogue File number will be displayed in BCD.  If you want to change this,
simply use the last two rows of keys to toggle the bits of the BCD number.  A green LED means the bit is
zero (0); a red LED means the bit is one (1).  You may press as  many keys as needed to  make up the
desired number.  For the example, to make the Dialogue File 24, LEDs 11 and 14 need to be switched
Red the rest of the LEDs should be green.  Once this LED pattern is set press the [5] key again to enter
this new value into memory.  

Note:

 If you don't press the [5] key a second time the changes will not be

saved.

<

If your entry is accepted, the LEDs will turn off with the exception of the Operating Mode LED.  If there is a
problem with your entry, the last two rows will flash amber and the 9605 will reject the new value.  It will
return you to the parameter where you can adjust it to an acceptable value.

<

Repeat the steps mentioned above to change any or all of the remaining setup parameters to match the
application needs.  Keep in mind that SLC-500 uses the OCTAL numbering system for node addresses. 
In that system any number with 8 or 9 is invalid, therefore keys 9 and 13 (normally used as BCD 8 for
other Setup parameters) will be disabled on the 9605 to prevent an illegal station address from being
entered.

<

When the setup of the 9605 is complete, it is a good idea to view all of the setup parameters a second
time to insure that the proper values were entered in properly.

<

When satisfied with the setup of the 9605, the slide switch must be placed in the off position.  Once the
proper communication cable is attached, the 9605 can attempt to establish communications with the
processor by either pressing the [7] key (RESTART) or by cycling power to the 9605.

Summary of Contents for 9605

Page 1: ...ll QUARTECH CORPORATION be responsible or liable for any damage including indirect or consequential losses resulting from the use misuse or application of the unit The text illustrations charts and ex...

Page 2: ...Image bits Mode B 3 2 3 Switch Image bits Mode A 3 2 4 Green Amber Red LED bits Mode A only 4 2 5 Switch Configure Bits 4 2 6 Watchdog Timer Option 5 Section 3 Setup Mode 6 3 1 Using the Setup Mode 6...

Page 3: ...nication interface modules or Input Output modules to operate The 9605 connects directly to the SLC 500 s DH port When the 9605 is powered up the LEDs will imediately display a version number before i...

Page 4: ...an 99 For example a valid Dialogue File would be B 10 The Dialogue File must be at least 2 elements 0 and 1 for operating Mode B or at least 5 elements 0 thru 4 for operating Mode A If these elements...

Page 5: ...ad the status of the switch image bits from the SLC 500 then if the switch is pressed it will compliment the state of the associated register bit For example if the register bit is energized and the s...

Page 6: ...ergized For example to light LED 10 red bit number 09 of the red register must be energized A priority scheme exists so that if more than one color register bit is energized for the same LED the outco...

Page 7: ...ering the file number and the element number during the setup of the 9605 see section 3 The 9605 will write a value of zero 0 to the accumulator of this timer on a regular and continuous basis therefo...

Page 8: ...on the EEPROM cannot be changed With this in mind the slide switch should be kept off whenever the 9605 is not in Setup mode This will assure that the 9605 s setup data is safe Slide switch down towar...

Page 9: ...one 1 You may press as many keys as needed to make up the desired number For the example to make the Dialogue File 24 LEDs 11 and 14 need to be switched Red the rest of the LEDs should be green Once...

Page 10: ...ent each individual digit of the decimal number The table to the left shows the possible combinations for a one digit decimal number The bits of the BCD number sum to equal the decimal digit if each b...

Page 11: ...nate upon pressing a particular key If the LED does not illuminate with the action of the switch the keyboard may be damaged 2 LED test This test will prove that power is reaching all of the printed c...

Page 12: ...ct between multiple SLC 500 s that may be on the network The physical connection between the 9605 and SLC 500 processor is through the Three position terminal block The 9605 provides both a nine pin D...

Page 13: ...cted at each end of the trunkline to provide proper line loading thus reducing signal interference Devices intended for use on the DH network must include as part of their interface hardware a line te...

Page 14: ...isy power supply voltage Slide switch was left in the on position It should only be on during Setup Mode 15 EEPROM write disabled Slide switch is not in the on position 21 No activity on the network C...

Page 15: ...t a timer file Not enough WD file elements The WD File entered during setup does not exist in the PLC or it is not a timer file The timer file may not be large enough to contain the element selected d...

Page 16: ...pplications Environment Operating Temperature 0 c to 60 c Storage Temperature 20 c to 70 c Operating Humidity 0 to 95 non condensing Storage Humidity 0 to 95 non condensing Vibration 10Hz to 55Hz Disp...

Page 17: ...rsof type 12 cpi The strip measures 4 x 0 7 inches 0 01 inch max thickness Quartech can provide custom legends produced to your specifications Custom graphics and color may be included in each legend...

Page 18: ......

Reviews: