WARNING: DO NOT OPERATE UNIT UNLESS ALL FILTERS ARE IN PLACE.

 

RESETTING MICROPROCESSOR AFTER FILTER(S) HAVE BEEN REPLACED 

Resetting Microprocessor After FILTER Replacement ,  

WHILE “Service Filters” Led is SOLID 

1- 

Ensure motor access door is closed 

2- 

Plug power back to the unit 

3- 

When you Press “POWER”, MOTOR WILL START, “Service FILTER(s)” Led stays SOLID 

4- 

While motor is operating, press & hold SPEED UP & DN simultaneously until unit BEEPS 

 

(hold for 10+ seconds, when beeping continuously, release) 

5- 

In this condition, “System ON” Led is FLASHING, “Service Filters” led is SOLID 

6- 

Press SPEED DN until “Service Filters” Led is FLASHING and system is BEEPING continuously 

7- 

Press & HOLD POWER button while “Service Filters” is FLASHING & BEEPING continuously 

 

Release, when it stops BEEPING 

8- 

Led will be OFF and unit will be ready to operate again 

 

Resetting Microprocessor After Filter Replacement,  

WHILE “Service Filters” Led is OFF 

1- 

Ensure motor access door is closed 

2- 

Plug power back to the unit 

3- 

When you Press “POWER”, MOTOR WILL START 

4- 

While motor is operating, press & hold SPEED UP & DN simultaneously until unit BEEPS 

 

(hold for 10+ seconds, when beeping continuously, release) 

5- 

In this condition, “System ON” Led is FLASHING 

6- 

Press SPEED DN until “Service Filters” Led is FLASHING 

7- 

Press & HOLD POWER button while “Service Filters” is FLASHING,  

Release, when it stops BEEPING 

8- 

Led will be OFF and unit will be ready to operate again 

BLOWER MAINTENANCE – INFINITY MOTORS, NO BRUSH CHANGE REQUIRED 

This unit is equipped with an Automatic Motor Optimization System.  Motor is equipped with EXTENDED LENGTH MOTOR BRUSHES.  Estimated duration can 
be up to 2000-4000 hours and  is dependent on many factors such as continuous use and motor speed.  To avoid downtime “Service Motor(s) Led will illuminate 
when motor is approximately 90% worn.  This allows you the time to purchase new motors, and have them available for when the motors expire. 
When Automatic Motor and Brush Optimization System estimates motor(s) have been worn to dangerous level, appropriate LED will illuminate. 

 

To optimize and ensure longest motor life, AFTER REPLACEMENT, START motor right away reset the LED as per instructions below, 

speed will automatically 

default to LOW

.  Operating the motor at Low speed for 15 minutes will “break-in” the new motor, optimizing and prolonging their life. 

 

WARNING:  Switch unit off and unplug power cord from wall before servicing the blower. 

TURN UNIT UPSIDE DOWN, Access to the motors is through the bottom plate as pictured below.  

 

 

 

 

Motor section from outside 

 

    Motor section from inside 

 

Motors close-up, with support

 

Filter Bags (AG259 or AG149 depending on your application) located behind front access door 
 

Separation grille: 
Must be placed right below FILTER BAGS, so the filter below the Filter Bags does not clog 

 
Odor Filter (Not Pictured)

 located below Filter Bags (above HEPA Filter). Part number varies by application. 

Not required for all applications. (ALWAYS PLACE SEPARATION GRILLE ABOVE ODOR FILTER) 

 
HEPA Filter (F074)

 located at bottom below the filters, behind front access door. 

Summary of Contents for CollectALL MedEVAC MultiPure PowerStation PS2

Page 1: ...unit 6 ft long hose INSTALLATION 1 Open filter door remove plastic around HEPA filter and Odor Filter if applicable 2 Ensure filter bags are properly installed fit into 2 tubes beneath the top of fil...

Page 2: ...companies shipping documents Single box c w all components required either on or inside the unit PRE START UP CHECKLIST a Check that all internal components are present and are adequately supported b...

Page 3: ...t stops BEEPING 8 Led will be OFF and unit will be ready to operate again BLOWER MAINTENANCE INFINITY MOTORS NO BRUSH CHANGE REQUIRED This unit is equipped with an Automatic Motor Optimization System...

Page 4: ...et design See the beginning of the Motor Service Replacement Section 5 Install the bracket on the new motor If the bracket is installed incorrectly it may result in a short to ground for the brush con...

Page 5: ...r s Led stays SOLID 4 While motor is operating press hold SPEED UP DN simultaneously until unit BEEPS hold for 10 seconds when beeping continuously release 5 In this condition System ON Led is FLASHIN...

Page 6: ...sed to assume for QUATRO any other liability in connection with the sale of these goods Equipment parts and material manufactured by others and incorporated in QUATRO s equipment are warranted by QUAT...

Page 7: ...ming Urgent Replace Filters See Filter Service Replacement For More Info Continued Operation May Result In Unit Shutdown High Pressure Causes Excess Motor Heat Accelerates Brush Wear Flashing Slowly B...

Page 8: ...n removed Remote has a shutdown delay of approximately 5 10 seconds Flashing None Unit is in Standby mode waiting for remote signal or mc2 signal if provided to start unit Low System Pressure Flashing...

Reviews: