Jet-Stream Tall Operation & Maintenance Manual
i Series Controls
WARNING:
RESPECT THE INDICATED POLARITY WHEN MAKING THIS CONNECTION .
DO NOT EXCEED 30V
Remote Operation
•
If choosing the Dry Contact (closed contact) remote option, connect the black and red wires to anything that can close
a contact and short these 2 wires together .
•
If choosing the 1-30V AC/DC remote option, connect the white and the green wires to the remote signal .
AC/DC.
To enable the remote system startup for either remote option, first plug the system into power and then connect remote
cable . Then simply have the other piece of equipment close (short) the dry contact or supply a remote control voltage .
When the unit is stopped the QUATRO System will shut down after a short delay .
After Remote Sensing Has Been Activated:
•
If the unit is RECEIVING a remote signal: System ON and Remote ON Lights will be FULLY Illuminated
•
If the unit is WAITING FOR a remote signal: System ON will be OFF and Remote ON Lights will be FLASHING
Unplugging the power cord will automatically deactivate Remote Sensing Feature .
Remote Status
The System can output status signals to your equipment .
•
The
Run Signal
contact is CLOSED whenever the system is turned on (motor(s) are functioning) .
The contact is OPEN when the unit is turned off (motor(s) are not functioning). This includes when the unit goes into
Remote/Standby and if the unit shuts down due to a problem .
Run signal will NOT open when the motor(s) shut off for a filter cleaning when operating in “Online” filter cleaning
mode. Critical Filter Pressure Alarms (high and low pressure) will OPEN the Run Signal and shut the motor(s) off.
•
The
Fault Signal
can be used either with a Normally Open (NO) or Normally Closed (NC) contact depending on
which wire you choose to use (see diagram on previous page) .
When there ARE NO alarm conditions present the NO contact will remain open and the NC contact will remain closed .
When there ARE alarm conditions the NO contact will CLOSE and the NC contact will OPEN .
ALL LEVELS of Filter and Motor(s) service alarms will trip the Fault Signal .
The Quatro Run Signal can only shut down the piece of equipment controlling it remotely if the piece of equipment
supports that function. The piece of equipment must be set or programmed to shut itself off when the Quatro Run signal is
OPENED . Contact your equipment manufacturer to verify if your equipment supports that function .
The status signals can either return a “signal” provided by your equipment or output a 12VDC+ or 12VDC-, depending on
how the AE427 remote cable is wired . The Quatro System uses a single “common” for both the Run and Fault Signals .
a . To return a “signal” connect your signal to the Brown wire (Pin 5) .
•
The “returned” Run signal is available on the Violet wire (Pin 9) .
•
The “returned” Fault NC (Normally Closed) is available on the Blue wire (Pin 6) .
•
The “returned” Fault NO (Normally Open) is available on the Orange wire (Pin 7) .
b . To be supplied with a 12vdc signal where the + is being switched, connect the Yellow Wire (Pin 8) to the Brown wire