11. Flush Shutter DC Calibration
Automatic calibration
Automatic calibration is a process during which the Flush Shutter DC learns the position of the
limit switches.
Shutter positioning calibration
(par. 71 set to 0)
There are two options to calibrate the device:
•
Calibration through main controller UI
1) Include the module into the Z-wave network according to the instructions for inclusion.
2) Set the parameter 78 (Forced Flush Shutter DC calibration) value to 1.
3) Flush Shutter DC performs the calibration process, completing full cycle - up, down and
up again.
4) Set the parameter 78 (Forced Flush Shutter DC calibration) value to 0.
•
Calibration through the inputs I1 and I2
1) Include the module into the wireless network, according to the instructions for inclusion.
2) Quick press the switch/push-button connected to I1 input and wait until the Shutter DC
reaches the upper limit switch.
3) Quick press the switch/push-button connected to I2 input and wait until the Shutter DC
reaches the lower limit switch.
4) Quick press the switch/push-button connected to I1 input and wait until the Shutter DC
reaches the upper limit switch.
Slates tilting position calibration
(par. 71 set to 1)
When enabling venetian blind mode, position calibration for slats titling must be done. After
doing this, position and angle of slates can be set. By default, full turn time for slates is set to
1.5s. This value can be changed with parameter 72.
1) Include and make module calibration according to section ‘Shutter positioning calibration’.