EN
.
44
13. Flush Shutter Operation
Automatic calibration
Automatic calibration is a process during which the Flush Shutter learns the position of the limit
switches.
Shutter positioning calibration
(par. 71 set to 0)
•
Calibration through the main gateway (hub) UI
1) Include the device into the Z-Wave network according to the instructions for inclusion.
2) Set the parameter 78 (Forced Flush Shutter calibration) value to 1.
3) Flush Shutter performs the calibration process, completing full cycle - up, down and up
again.
Slates tilting position calibration
(par. 71 set to 1)
When enabling venetian blinds mode, position calibration for slats titling must be done. After
doing this, the position and angle of the slates can be set. By default, full turn time for slates is
set to 1.5s. This value can be changed with parameter 72.
1) Include and perform the device calibration process according to
section ‘Shutter positioning
calibration’.
2) Set parameter 71 to 1 ‘Venetian blinds’.
3) Exclude the device (without reset!).
3) Wait 30 seconds.
4) Include the device.
5) After the device will be included, another widget (besides the main Shutter widget) for slates
control will appear on the UI.
Summary of Contents for Flush Shutter
Page 3: ...EN 3 18 Warning 64 19 Regulations 64 ...
Page 19: ...EN 19 4 Package Contents Flush Shutter Device Installation Manual ...
Page 21: ...EN 21 ...
Page 25: ...EN 25 After Qubino installation ...
Page 31: ...EN 31 Step 2 Switch of the power supply Step 3 Connect the temperature sensor as shown below ...
Page 32: ...EN 32 Step 4 Place the temperature sensor in the switch box Step 5 Turn the fuse on ...
Page 33: ...EN 33 Step 6 Re include the device to your network ...
Page 34: ...EN 34 Step 7 Start using the temperature sensor in connection with your device ...