background image

6

7

4.2 MODE 2 OPERATION

1. The element is energised, allowing heating 

of the water to take place.

2. The continued heating results in the water 

reaching the set point, detected by the 

Thermistor.

3. The Solenoid Valve is then energised,  

allo wing ambient water to enter the tank 

thus reducing the water temperature by a 

maximum of 2°C and results in a shift away 

from the set point, again detected by the 

thermistor.

4. When this occurs, the solenoid valve is 

then de-energised, stopping the flow of 

water into the tank.

5. Steps 2 to 4 are repeated until the High 

Level Probe becomes “CLOSED”, i.e. water is 

present.

4.3 MODE 3 OPERATION

1. The Element remains energised, allowing 

heating of water to take place, resulting in 

the water attaining set point, detected by 

the Thermistor.

2. The Element is then de-energised allowing 

cooling of water to take place.

3. Cooling continues to take place through 

heat loss via the tank insulation until set 

temperature point minus 2°C is reached, 

detected  by the Thermistor.

4. The Element is then energised, allowing 

heating of water to take place.

5. Steps 1 to 4 are repeated until the water 

is drawn from the unit, at which time the 

controller then steps back into MODE 2.

4.4 

4.5. DIAGRAM: DIMENSION SPECIFICATION 2.5L, 5L, 7.5L, 10L, 15L MODELS

DIMENSION 

SPECIFICATION 

TABLE 

– referring to diagram 

on the next page

WB-BW-AQ2.5L/5L/7.5L/IOL/15L

WB-BW-AQ25L 

E

E

Summary of Contents for WB-BW-AQ

Page 1: ...INSTANT BOILING WATER DISPENSER Installation Guide Owner s Manual WB BW AQ ...

Page 2: ...erature is not more than 45 C Prohibition of outdoor use 1 2 Please ensure that the mains cold water supply is connected to the indicated water inlet connection of the Boiling Water Unit at the base of the solenoid valve and that the unit vent connection always has a free flow of air into and out of the boiling water chamber 1 3 The Boiling Water Unit is a simple tech nologically advanced electron...

Page 3: ...ine no more than 300 mm from the Boiling Water unit 3 7 DRAIN CONNECTION There is a drain screw located on the under side of the unit to completely drain the tank for servicing Before removing the drain screw ensure the appliance has been switched off and the water is not hot enough to scald CAUTION This unit is not suitable for installation in an area where a water jet could be used This unit mus...

Page 4: ...water is present 4 3 MODE 3 OPERATION 1 The Element remains energised allowing heating of water to take place resulting in the water attaining set point detected by the Thermistor 2 The Element is then de energised allowing cooling of water to take place 3 Cooling continues to take place through heat loss via the tank insulation until set temperature point minus 2 C is reached detected by the Ther...

Page 5: ...hermistor failure Reset the Thermal cut out If the Heating Element is properly wired then check its resistance Test the Electronic Controller Replace Thermistor 3 The unit boils continuously Temperature is not correctly set Electronic Controller failure Thermistor failure Set the Temperature Adjustment Trim Pot Test the Electronic Controller Replace Thermistor 4 The unit overflows Incoming water p...

Page 6: ...10 11 7 SPARE PARTS LIST 8 NOTES ...

Page 7: ......

Reviews: