background image

6

QUEST 506 

 

                                                   INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

QUESTCLIMATE.COM

(877) 420-1330

4.3 CONDENSATE WATER REMOVAL

Condensate drains by gravity via the drain port. Use 3/4” male NPT PVC pipe. An optional 
condensate pump kit may be installed if a lift is required to dispose of the condensate. Optional parts 
list for information on the kit. 

FOLLOW DIAGRAM:

•  Level within 2°

Vent:

•  Place vent after the trap.

•  Vent should be open.

•  Height of vent should be higher than drain outlet.

Cap:

•  A clean out can be placed before trap but must be 

sealed with a cap.

Drain Line:

•  Drain line should go in a downward slope to the drain.

•  1/4” drop per foot.

4.4 HANGING DIAGRAM

PARTS NEEDED:

 

4 pieces 3/8” threaded rod (not included) 

 

 

4 - 3/8” threaded jam nuts (not included)

 

WARNING!

 

 

Hanging installation must meet all state and local codes.

28.95

27.25

3/8” threaded rod

Intake Air

Treated Air

3/8” Jam Nuts

5.56”

Drain Trap Configuration

VENT OPEN

CAP

2”

6.75”

4”

3/4” drain port

Summary of Contents for 506

Page 1: ...O M 87 7 420 1330 Patents thermastor com patents Serial Number Install Date Sold By T S 10 16 01 2 2 R E V J Quiet operation 230V 277V units Long life impeller Industry leading efficiency Superior MERV 13 air filtration Environmentally friendly refrigerant Auto restart after power outages ...

Page 2: ...e Water Removal 6 4 4 Hanging 6 5 Controls 7 5 1 Humidity Control 7 5 2 24VAC Wiring 7 5 2A Deh 3000R 8 5 2B Honeywell Remote Humidistat 8 5 2C Daisy Chain 8 6 Maintenance 8 6 1 Standard Air Filter 9 7 Service 9 7 1 Warranty 9 7 2 Technical Description 9 7 3 Troublshooting 9 8 Ducting Guidelines 11 Wiring Diagram 12 Service Parts List 13 Optional Parts List 13 Warranty 14 4201 Lien Rd Madison WI 5...

Page 3: ... or table DO NOT place the device directly on structural members Provide vibration isolation in order to minimize operational vibration and or noise A drain pan MUST be placed under the unit if installed above a living area or above an area where water leakage could cause damage Never operate a unit with a damaged power cord If the power cord is damaged it must be replaced by the manufacturer its ...

Page 4: ...S 80 F 60 RH UNIT QUEST 506 4036600 QUEST 506 277V 4036610 CFM 1350 0 0 WG 1350 0 0 WG POWER 2700 Watts 2700 Watts SUPPLY VOLTAGE 220 240 VAC 1 Phase 60 Hz 277 VAC 1 Phase 60 Hz CURRENT DRAW 11 0A 10 0A RATED CURRENT DRAW AMPS 104 F 36 13 6A 12 2A ENERGY FACTOR 3 8 L kWh 3 8 L kWh OPERATING TEMP 56 F Min 95 F Max 56 F Min 95 F Max WATER REMOVAL EFFICIENCY 506 Pints Day 8 1 Pints kWh 506 Pints Day ...

Page 5: ... test These test should be performed by a qualified service person The Quest 506 dehumidifier plugs into NEMA 6 20R rated receptacle The Quest 506 277v dehumidifer plugs into a NEMA L7 20P rated receptacle The amp draws are listed on page 4 of this manual Connecting to electrical power must comply with all national state and local electrical codes A ground fault interrupter protected circuit is re...

Page 6: ...thin 2 Vent Place vent after the trap Vent should be open Height of vent should be higher than drain outlet Cap A clean out can be placed before trap but must be sealed with a cap Drain Line Drain line should go in a downward slope to the drain 1 4 drop per foot 4 4 HANGING DIAGRAM PARTS NEEDED 4 pieces 3 8 threaded rod not included 4 3 8 threaded jam nuts not included WARNING Hanging installation...

Page 7: ...ent by the remote humidistat signals the fan or fan and compressor to actuate QUEST CONTROL OPTIONS Cloud Control Quest DEH3000R Honeywell Humidipro Any 24V signal to Dehumidify CAUTION Low Voltage Hazard Can cause equipment damage Disconnect power before beginning installation 5 2 24VAC WIRING The terminal block low voltage circuit breaker and power switch are located on the intake side of the un...

Page 8: ... C FAN R DHUM COMPRESSOR AND FAN FLOAT FLOAT 24VAC COMP FAN QUEST DEH 3000R CONTROLER C FAN R DHUM COMPRESSOR AND FAN FLOAT FLOAT C FAN R DHUM COMPRESSOR AND FAN FLOAT FLOAT QUEST 6 SERIES UNIT 2 C FAN R DHUM COMPRESSOR AND FAN FLOAT FLOAT QUEST 6 SERIES UNIT 3 QUEST 6 SERIES UNIT 1 NOTE DO NOT WIRE IN FAN TERMINAL WITH THIS APPLICATION C FAN R DHUM COMPRESSOR AND FAN FLOAT FLOAT 24V IN COM 24V OU...

Page 9: ...ECHNICAL DESCRIPTION NON STANDARD PATENTED The Quest 506 Dehumidifier uses a refrigeration system similar to an air conditioner s to remove heat and moisture from incoming air and add heat to the air that is discharged Hot high pressure refrigerant gas is routed from the compressor to the condenser coil The refrigerant is cooled and condensed by giving up its heat to the air that is about to be di...

Page 10: ...t as much as expected 1 Air temperature and or humidity have dropped 2 Humidity meter and or thermometer used are out of calibration 3 Unit has entered defrost cycle 4 Air filter dirty 5 Defective defrost sensor 6 Low refrigerant charge 7 Air leak such as loose cover or ducting leaks 8 Defective compressor 9 Restrictive ducting 10 Optional Condensate Pump Safety Switch open Test to determine if th...

Page 11: ... location Intake and exhaust ducting should have a minimum of 4 feet from the unit before any turns CAUTION Do not connect with a static pressure greater than 25 wg Contact technical support for additional details Optional duct kits are available from the factory Exhaust Kit 4038641 and Intake Kit 4038642 See figures below for plenum dimensions and duct diameters Alternatively licensed contractors...

Page 12: ...12 QUEST 506 INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS QUESTCLIMATE COM 877 420 1330 WIRING DIAGRAM OF THE QUEST 506 DEHUMIDIFIER ...

Page 13: ...4037703 04 COIL EVAP 15 4037704 02 COIL CONDENSER 16 4037707 TXV 3 TON 17 4037708 FAN MOTORIZED IMPELLER 4042941 FAN MOTORIZED IMPELLER 277V 18 4037728 CORD 4042899 CORD 277V 19 4038135 HANDLE POCKET 20 4038136 BEZEL HANDLE 21 4038178 WIRE HARNESS 22 4038079 LUG GROUND 23 4038219 FOOT RUBBER 1 25 DIA 24 4038225 01 BRACKET FOOT RIGHT 25 4038226 01 BRACKET FOOT LEFT 26 4038215 BLOCK WIRING 27 403969...

Page 14: ... means The end user is responsible for normal care This warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or installation accident acts of nature or any other cause beyond Therma Stor LLC s reasonable control LIMITATIONS AND EXCLUSIONS If any Quest 506 Dehumidifier part is rep...

Reviews: