background image

Quest CDG 174 

Installation, Operation and Maintenance Instructions

  

1-877-420-1330

 

5

www.QuestHydro.com

info@QuestHydro.com

2.3 Electrical Requirements

The Quest CDG 174 can be plugged into a grounded 15 Amp circuit. At 80°F, 60% RH, it draws 10 Amps. Due to the 

high percentage of a 15 Amp circuit’s capacity that the unit uses, the circuit should be dedicated to running it only. Amp 

draw decreases at lower loads and increases at higher loads. At extremely high loads, a 20 Amp circuit may be required.
If an extension cord is required, it must have a minimum of 12 gauge conductors if 25 feet long or less and 10 gauge 

conductors if greater than 25 feet long.

2.4 Condensate Removal

The Quest CDG 174 is equipped with an internal condensate pump to remove the water that is condensed during 

dehumidification. This allows the condensate to be pumped 30’ with the attached hose. If the condensate must be 

pumped more than 20 feet above the unit, a second pump must be added to relay the condensate.

2.5 Ducting

A detachable rectangular exhaust collar is supplied that will allow 10” round lay-flat duct to be attached to the Quest 

CDG 174 outlet. 
To attach ducting to a collar, put the plastic duct end through the collar center and roll the duct end outward so that it 

overlaps the outside of the collar. The duct and collar may then be quickly attached to the Quest CDG 174 by snapping 

the collar over the four screws at the blower outlet. 

2.6 Power Button

Press the POWER button to turn the dehumidifier on or off. When starting the dehumidifier the display will show the 

accumulated hours. Press the POWER button again to turn the dehumidifier off. The display will also power off.

2.7 Pump Purge Button

During normal operation the pump automatically cycles every four minutes. Press the PURGE button to remove 

condensate manually from the reservoir. There are several ways to manually remove water from the reservoir:
1.   Press the PURGE button once and the pump will run for 20 seconds
2.   Press and hold the PURGE button and the pump will run for up to 30 seconds
3.   Press the PURGE button while the dehumidifier is powered off and the pump will run for 30 seconds.
Always manually purge the water reservoir before transport or storage. Turn off the power and allow the plugged in dehu-

midifier to rest 15 minutes before the final purge.

2.8 Humidistat

Adjust the humidistat to the desired conditioned humidity. The humidistat has a range of 20% to 70% RH. “ON” will 

operate the unit continuously regardless of humidity.

2.9 Hours Button

Pressing the HOURS button displays the hour meter when the unit is turned off but plugged into power.   To reset job 

hours, press and hold the HOURS button for 5 seconds when the unit is operating. 

Summary of Contents for CDG 174

Page 1: ...oceed successfully Ultimate satisfaction depends on the quality of installation and a thorough understanding of this equipment The dehumidifier is built around tested engineering principles and has pa...

Page 2: ...5 2 5 Ducting 5 2 6 POWER Button 5 2 7 PURGE Button 5 2 8 Humidistat 6 2 9 HOURS Button 6 2 10 DEFROST Light 6 2 11 Defrost Cycle 6 2 12 Low Pressure Control 6 3 Maintenance 7 3 1 Air Filter 7 3 2 Sto...

Page 3: ...nd service DO NOT INSTALL UNIT WITH THE SERVICE PANELS INACCESSIBLE Avoid directing the discharge air at people or over the water in pool areas If used near a pool or spa be certain there is NO chance...

Page 4: ...sate hose into a drain or a very large container and turn on To decrease drying times make sure all windows and doors are closed to the outside and seal off the wet area from any unaffected areas 2 1...

Page 5: ...it overlaps the outside of the collar The duct and collar may then be quickly attached to the Quest CDG 174 by snapping the collar over the four screws at the blower outlet 2 6 Power Button Press the...

Page 6: ...evaporator temperature does not reach the desired temperature the compressor will start after 15 minutes The system will start a timed defrost cycle The timed defrost cycle ensures the unit will cont...

Page 7: ...evel in the reservoir 5 Flush with water 4 Service CAUTION Servicing the Quest CDG 174 with its high pressure refrigerant system and high voltage circuitry presents a health hazard that could result i...

Page 8: ...d POWER button does not turn ON 1 Unit unplugged or no power to outlet 2 Defective control board 3 Loose connection in internal wiring No dehumidification neither hour meter display nor compressor run...

Page 9: ...ycle 5 Air filter dirty 6 Defective defrost thermistor 7 Low refrigerant charge 8 Air leak such as loose front cover 9 Defective compressor 10 Restrictive exhaust or inlet ducting Unit runs but does n...

Page 10: ...ure in reverse 4 6 Thermistor Replacement The defrost thermistor probe is inserted into the coil measuring coil temperatures and reacts accordingly To replace thermistor 1 Remove top cover and filter...

Page 11: ...the plastic plug on the right side see Fig 4 out from inside the unit 3 Locate the heavy vinyl hose that connects the drain pan to the condensate pump Pull the end out of the pump 4 Remove tie wrap h...

Page 12: ...4 1 COMPRESSOR RELAY LOW PRESSURE SWITCH COMPRESSOR R C S PUMP NC NO YEL TERMINAL BLOCK WIRE CAPACITOR COMPRESSOR CAPACITOR IMPELLER SAFETY PROBE IMPELLER CAPACITOR 2 6 20 BLK 13 16 19 WHT 12 WHT 9 1...

Page 13: ...citor Impeller 15mfd 371V 1 4035235 07 14 Thermistor not shown 1 4034716 01 15 Cord 14ga 25 1 4037569 16 Compressor 11 9KBTU R410a 1 4034763 17 Overload Compressor 1 4034033 18 Evaporator Coil 1 40344...

Page 14: ...The end user is responsible for normal care This warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthori...

Reviews: