background image

1-866-933-7486 

Quest Dry RDS 10 

Installation, Operation and Maintenance Instructions

  

5

www.QuestOnTheJob.com

sales@QuestOnTheJob.com

Quest Dry RDS 10 

Installation, Operation and Maintenance Instructions

  

quest

quest

3.2 Electrical Requirements

The Quest Dry RDS 10 plugs into a common grounded outlet on a 15 amp circuit. It draws 5.1 amps at 80°F, 
60% RH. If used in a wet area, a ground fault interrupter (GFI) is required. If an extension cord is required, it 
must have a minimum of 14 gauge conductors if 25 feet long or less and 12 gauge conductors if greater than 
25 feet long. 

3.3 Condensate Removal

The Quest Dry RDS 10 is equipped with an internal condensate pump to remove the water that is condensed 
during dehumidification. This allows the condensate to be pumped 20 feet with the attached hose. If the 
condensate must be pumped more than 20 feet above the unit, a second pump must be added to relay the 
condensate. The condensate pump automatically purges for 20 seconds every eight minutes. Use the PURGE 
button to manually remove condensation.

3.4 Ducting

A wire duct collar is supplied to allow 10” lay-flat duct to be attached to the Quest Dry RDS 10 outlet. Lay-
flat plastic ducting is available; see accessories table page 6. To attach ducting to the wire duct collar, put 
the plastic duct end through the collar center and roll the duct end outward so that it overlaps the outside of 
the collar. The duct and collar may then be quickly attached to the Quest Dry RDS 10 by snapping the collar 
over the four exhaust tabs.

3.5 Defrost Cycle

If the low side refrigerant temperature drops due to excessive frost 
formation on the evaporator coil and below the temperature set 
point, the thermistor activates the solid-state control and defrost 
light. The compressor is cycled off and on by the thermistor 
temperature measurement. The air mover will continue to run, 
causing air to flow through the evaporator coil and melt the ice 
when the compressor is off. When the air temperature and/or 
humidity increases, the evaporator temperature will rise and the 
thermistor will end the defrost cycle at the temperature set point.

3.6 POWER Button

Press the POWER button to turn the dehumidifier on or off. When starting the dehumidifier the display will 
show the accumulated hours. Press the POWER button again to turn the dehumidifier off. The display will 
also power off.

3.7 PURGE Button

During normal operation the pump automatically cycles every four minutes. Press the PURGE button to 
remove condensate manually from the reservoir. There are several ways to manually remove water from the 
reservoir:

1.  Press the PURGE button once and the pump will run for 20 seconds
2.  Press and hold the PURGE button and the pump will run for up to 30 seconds
3.  Press the PURGE button while the dehumidifier is powered off and the pump will run for 30 seconds.
Always manually purge the water reservoir before transport or storage. Turn off the power and allow the 
plugged in dehumidifier to rest 15 minutes before the final purge.

Figure 2: Quest Dry RDS 10 control board.

Summary of Contents for Dry RDS 10

Page 1: ...built around tested engineering principles and has passed a thorough inspection for quality of workmanship and function 4201 Lien Rd Phone 608 237 8400 Madison WI 53704 Toll Free 1 866 933 7476 www Q...

Page 2: ...3 Operation 4 3 1 Transporting 4 3 2 Electrical Requirements 5 3 3 Condensate Removal 5 3 4 Ducting 5 3 6 POWER Button 5 3 7 PURGE Button 5 3 8 Hour Meter 6 3 9 HOURS Button 6 3 10 DEFROST Light 6 4...

Page 3: ...power cord If the power cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified person in order to avoid a hazard The unit shall be installed in accordance wi...

Page 4: ...th year 100 of Parts of sealed refrigeration system Dimensions Width 20 Depth 20 Height 33 Weight 105 lbs Patent 7 246 503 3 Operation Place dehumidifier inside structure place condensate hose into a...

Page 5: ...y then be quickly attached to the Quest Dry RDS 10 by snapping the collar over the four exhaust tabs 3 5 Defrost Cycle If the low side refrigerant temperature drops due to excessive frost formation on...

Page 6: ...acity and efficiency and may cause the compressor to cycle off and on unnecessarily The filter can generally be vacuumed clean several times before needing replacement Replacement filters can be order...

Page 7: ...hen passes through a filter drier and capillary tubing which cause the refrigerant pressure and temperature to drop It next enters the evaporator coil where it absorbs heat from the incoming air and e...

Page 8: ...sed check pump reservoir 3 Defective compressor capacitor 4 Defective compressor overload 5 Defective compressor 6 Defective control board Air mover does not run Compressor runs briefly but cycles on...

Page 9: ...The motorized impeller has a PSC motor and internal thermal overload protection If defective the complete assembly must be replaced 1 Unplug power cord 2 Remove the four screws attaching the bottom pl...

Page 10: ...te reservoir The float safety switch turns off the compressor until the water level lowers and disengages the switch To replace the float safety switch 1 Unplug the dehumidifier 2 Remove the front hou...

Page 11: ...st Dry RDS 10 Installation Operation and Maintenance Instructions quest quest BLU 14 RED 13 COMPRESSOR BLOWER MOTOR LEVEL SWITCH CONTROL BOARD THERMISTOR CONDENSATE PUMP WHT 10 GRN BLK WHT 2 YEL 9 YEL...

Page 12: ...Wheel 2 4027138 10 Filter 12 x 12 x 1 1 4026315 11 Hose 1 4 ID x 33 long 1 4024916 12 Coupling Body 1 4 Tube 1 4026306 13 Coupling Insert 1 4 Tube 1 4026986 14 Cord 1 4032297 15 Control Board 1 402676...

Page 13: ...on request by use of the warranty card or other reasonable and reliable means The end user is responsible for normal care This warranty does not cover any defect malfunction etc resulting from misuse...

Reviews: