background image

Quest H5 

Installation, Operation and Maintenance Instructions  

5

1-877-420-1330

www.QuestClimate.com

info@QuestClimate.com

IMPORTANT: Total amperage of the H5 plus all devices plugged into the receptacle must not exceed 12 amps. The 

circuit breaker will not allow for loads in excess of 12 amps, although there is a time delay before the overloaded circuit 

is broken.
IMPORTANT: When the Quest H5 is plugged into a standard “powered” wall outlet the Quest H5’s duplex outlet is 
electrically “HOT” and AC voltage is present

3.6 GFCI Protection and the On-Board Duplex VAC Outlet

The standard AC voltage outlet GFCI (Ground Fault Circuit Interrupter) protection promotes operator safety in wet 

applications. GFCI devices trip when a fault to electrical “ground” is sensed. 
It is recommended to check the GFCI protection prior to operation. To check, push the “TEST” button located on the 

GFCI duplex outlet. If operating properly the “RESET” button on the GFCI outlet will pop out. A tripped GFCI is 

indicated by a small LED. The device can only be “RESET” when the H5 is connected to a wall outlet providing standard 

voltage. This duplex AC outlet allows the inter-connection of other AC powered devices. The sum total amperage of all 

devices plugged into the receptacle must not exceed 10 amps.

3.7 Servicing

Before each use inspect for damage, blocked inlet or outlet.
Inspect the GFCI to ensure it is not in a “tripped” condition. Push “RESET” to reset the GFCI.
When the Quest H5 is first turned on, check for excessive vibration. If the unit vibrates excessively or if impeller rubs on 

housing, turn off the unit immediately. Have a service technician inspect the unit to locate the problem.

4. Maintenance

Use extreme caution when changing the HEPA filter as hazardous material could be trapped in the media. Always 

make sure to dispose of filters in the appropriate way. If you are unsure of how to safely dispose of any filter-consult an 

industrial hygienist to ensure that all hazardous materials are contained and disposed of properly. 

4.1 Air Filters

The standard Quest H5 HEPA System is equipped with two filters that progressively filter out smaller particles. 

An optional activated carbon/potassium permanganate filter can be also added. These filters must be checked 

regularly. Operating the unit with dirty filters will reduce the airflow, but will do no harm to the unit. The unit 

can be run indefinitely with dirty filters.
The two standard filters used are listed below (as installed in the unit from top to bottom):
A.  25 to 30% efficient (per ASHRAE 52.1-1992), MERV-7, pleated fabric pre-filter.
B.  99.97% DOP efficient HEPA filter.

4.2 Filter Replacement 

4.2A Filter Change Light

When the green “filter change light” illuminates. It may be time to replace one or both filters.

To check airflow accurately, an airflow meter or anemometer must be used:

When the filter change light illuminates; remove all ducting and run on high speed. if the filter light remains lit; replace 

the pre-filter and run on high again. If the light remains; it is time to replace the HEPA filter for full 500 CFM 

performance.

Summary of Contents for H5

Page 1: ...ested engineering principles and has passed a thorough inspection for quality of workmanship and function Installation Operation and Maintenance Instructions Read and Save These Instructions 1 Quest H...

Page 2: ...tlet Ducting 3 3 3C Negative Air Ducting 3 3 4 Power Speed Control 3 3 5 Resettable Circuit Breaker 4 3 6 GFCI Protection and On Board Duplex VAC Outlet 4 3 7 Servicing 4 4 Maintenance 4 4 1 Air Filte...

Page 3: ...et One foot minimum distance to obstructions Indoor use only Do not use as stool or bench Do not operate with damaged cord or plug Do not run cord under carpeting Do not cover cord with throw rugs run...

Page 4: ...an cause those devices to backdraft This can contaminate the space with potentially fatal gases In such cases the Quest H5 HEPA System must be used in one of the following three ways A As a filtering...

Page 5: ...CI When the Quest H5 is first turned on check for excessive vibration If the unit vibrates excessively or if impeller rubs on housing turn off the unit immediately Have a service technician inspect th...

Page 6: ...y use a blend of activated carbon and potassium permanganate This blend removes the vast majority of gaseous contaminants encountered in most filtering applications The activated carbon removes the he...

Page 7: ...ller Fan Speed Control 6 4032143 Impeller Fan Speed Control Knob 7 4037569 Cord 14ga 25 8 4033031 08 Run Capacitor 20 mfd 370 VAC 9 4031861 10 Lay flat duct collar ring Optional Parts Item Part No Des...

Page 8: ...Quest H5 Installation Operation and Maintenance Instructions 8 1 877 420 1330 www QuestClimate com info QuestClimate com...

Page 9: ...her cause beyond Therma Stor LLC s reasonable control If any Quest H5 part is repaired or replaced the new part shall be warranted for the balance of original warranty but all warranty periods will be...

Reviews: