Quest Oil Fired CHH-980 Installation, Operation and Maintenance Instructions
18
www.QuestProtect.com
sales@QuestProtect.com
4.8 Oil Burner Installation and Setup:
(Fig. 4)
• Refer to the Wayne FH burner Manual (which is included with this package) for detailed information and
instruction.
• Specific burner settings for the CHH-980 are as follows.
5. Operation
5.1 Startup
• Make sure the CHH-980 is connected to a correct, stable power source (120/240V, 50A, 60Hz, 4-wire
Grounding) and proper gauge chords are used (10 gauge minimum).
• Verify adequate and correct fuel supply (#1 or #2 light heating oil or diesel fuel). Refer to the name/
rating plate. Open all valves in the fuel-supply lines.
• With the main power switch (Fig. 14) in the OFF position, open the control panel door on the right (Fig.
11). Turn ON the three breakers (Fig. 19) and then close the panel.
• Turn ON the main power switch (Fig. 14). The white unit power light (Fig. 18) will come on, as well as
the two digital temperature gauges (Fig. 17) and hour meter (Fig. 12).
• Ensure that the HTF circuit valves are positioned for “Normal Single-pump operation” as in article 4.6
above.
• Turn ON only the primary pump switch (Fig. 15) and check the pump pressure gauge (Fig. 28). Steady
pressure around (35 to 45 PSI), indicates that no air remains in the fluid circuit. See article 4.4 above for
rapid air removal.
• Once a stable pump pressure is achieved, turn ON the burner switch (Fig. 16). The following sequence
should now occur: Observe the LED light cluster (Fig. 18).
-The glycol level light will turn on (indicating that there is a sufficient amount of HTF in the system).
-The high temp auto light will turn on. (This indicates that the high auto safety switch has not broken
the circuit).
-The high temp limit light will turn on. (This indicates that the high limit safety switches have not
broken the circuit).
-The high pressure limit switch light will turn on. (This indicates that the blocked flue high pressure
safety switch has not broken the circuit).
CHH-980
Wayne Burner Model
FH
Operational Mode
ON/OFF
Electrical Characteristics
V-A-Hz-Ph
120/11.5/60/1
Nozzle: Delavan Part #
2 required
2.75-60°B
Fuel Pump Pressure
PSI (Kpa)
162 (1117)
Fuel Input Rate: factory set
USGPH (Liters/Hr)
7.0 (26.5)
Heat Input: based on 140,000 Btu per USG
Btu/H (Kw/H)
980,000 (287)
Heat Output: @ 80% net efficiency
Btu/H (Kw/H)
784,000 (230)