34
GB
SBC NRG HIGH POWER - REV001A
NOTIFICATION SIGNS
STATUS MESSAGES
WARNING MESSAGES
COD.
MESSAGE
DESCRIPTION
71
BULK
The battery charger is in the BULK phase.
(See paragraph “OPERATION - Charging characteristics”).
72
ABSORPTION
The battery charger is in the ABSORPTION phase.
(See paragraph “OPERATION - Charging characteristics”)
73
FLOAT
The battery charger is in the FLOAT phase.
(See paragraph “OPERATION - Charging characteristics”)
74
Derating
The battery charger performs a limitation on the maximum output current due to a thermal problem, due a fan
which is not working or due low AC voltage.
75
Signal not expected in this model.
76
Monitor
The battery charger is in monitor mode
(See paragraph “BATTERY CHARGER PROGRAMMING-Secondary menu-monitor mode”).
77
Limit power
The manual mode of the maximum output current reduction has been activated.
(See paragraph “BATTERY CHARGER PROGRAMMING-Secondary menu-maximum output current”).
78
Silent mode
The silent mode for the cooling fans has been activated.
(See paragraph “BATTERY CHARGER PROGRAMMING-Secondary menu-silent mode”).
79
Sharing on
The battery charger is carrying out the current sharing with 2 or 3 battery chargers connected in parallel.
80
Charge comp
The battery charger is carrying out the batteries’ charge compensation according to their temperature.
Active only if the KTB4’S interface with the relevant sensor (not supplied) is connected to the system.
COD.
MESSAGE
DESCRIPTION
61
Batt M lo
The battery’s or battery bank’s voltage, measured on the MASTER output terminal, is lower than 11 Vdc
(mod. SBC 1200 NRG FR) or 22 Vdc (mod. SBC 1450 NRG HR, SBC 1950 NRG HR, SBC 2450 NRG HR).
As soon as the voltage goes back to a higher/equal value to 11 Vdc, the notification disappears
(mod. SBC 1200 NRG FR) or 22 Vdc (mod. SBC 1450 NRG HR, SBC 1950 NRG HR, SBC 2450 NRG HR).
62
Batt M hi
The battery’s or battery bank’s voltage, measured on the MASTER output terminal, is higher than 14,8 Vdc
(mod. SBC 1200 NRG FR) or 29,6 Vdc (mod. SBC 1450 NRG HR, SBC 1950 NRG HR, SBC 2450 NRG HR).
As soon as the voltage goes back to a lower/equal value to 14,8 Vdc, the notification disappears
(mod. SBC 1200 NRG FR) or 29,6 Vdc (mod. SBC 1450 NRG HR, SBC 1950 NRG HR, SBC 2450 NRG HR).
63
Batt 1 lo
The battery’s or battery bank’s voltage, measured on the SLAVE1 output terminal, is lower than 11 Vdc
(mod. SBC 1200 NRG FR) or 22 Vdc (mod. SBC 1450 NRG HR, SBC 1950 NRG HR, SBC 2450 NRG HR).
As soon as the voltage goes back to a higher/equal value to 11 Vdc, the notification disappears
(mod. SBC 1200 NRG FR) or 22 Vdc (mod. SBC 1450 NRG HR, SBC 1950 NRG HR, SBC 2450 NRG HR).
64
Batt 1 hi
The battery’s or battery bank’s voltage, measured on the SLAVE1 output terminal, is higher than 14,8 Vdc
(mod. SBC 1200 NRG FR) or 29,6 Vdc (mod. SBC 1450 NRG HR, SBC 1950 NRG HR, SBC 2450 NRG HR).
As soon as the voltage goes back to a lower/equal value to 14,8 Vdc, the notification disappears
(mod. SBC 1200 NRG FR) or 29,6 Vdc (mod. SBC 1450 NRG HR, SBC 1950 NRG HR, SBC 2450 NRG HR).
65
Batt 2 lo
The battery’s or battery bank’s voltage, measured on the SLAVE2 output terminal, is lower than 11 Vdc
(mod. SBC 1200 NRG FR) or 22 Vdc (mod. SBC 1450 NRG HR, SBC 1950 NRG HR, SBC 2450 NRG HR).
As soon as the voltage goes back to a higher/equal value to 11 Vdc, the notification disappears
(mod. SBC 1200 NRG FR) or 22 Vdc (mod. SBC 1450 NRG HR, SBC 1950 NRG HR, SBC 2450 NRG HR).
66
Batt 2 hi
The battery’s or battery bank’s voltage, measured on the SLAVE2 output terminal, is higher than 14,8 Vdc
(mod. SBC 1200 NRG FR) or 29,6 Vdc (mod. SBC 1450 NRG HR, SBC 1950 NRG HR, SBC 2450 NRG HR).
As soon as the voltage goes back to a lower/equal value to 14,8 Vdc, the notification disappears
(mod. SBC 1200 NRG FR) or 29,6 Vdc (mod. SBC 1450 NRG HR, SBC 1950 NRG HR, SBC 2450 NRG HR).