background image

14

Failures 

refers to EKCO.LN2 and EKCO.L2 boiler only

Symptom

Reason 

Action 

The indicators on 

control panel are off lack of boiler power supply

check parameters of the power network 

and fuses
contact an authorised service or the seller

A indicator flickers

insufficient pressure (below 0,5bar) switch the controller to the pressure view, 

increase the pressure to the required level 

pressure sensor failure 

switch the controller to pressure view, if 

the display shows „--” contact an author-

ised service

H indicator flickers

pump is blocked 

unblock  the  pump  -  unscrew  the  screw 

on  pump  housing  and  move  the  pump 

rotor manually 

a medium doesn’t circulate through 

the boiler – boiler is blocked 

an  air-bound  central  heating  system, 

vent the installation, pump and boiler
check patency of central heating system 

clean the filter

a failure of pump’s power supply  contact an authorised service or the seller
a failure of pump or flow sensor contact an authorised service or the seller

G indicator is off  

(in winter mode)

a  failure  of  installation  that  con-

nect a room thermostat

contact an authorised service or the seller 

a failure of electronic module 

contact an authorised service or the seller

K indicator flickers a  failure  of  inlet  temp.  sensor, 

boiler in failure condition 

contact an authorised service or the seller 

L indicator flickers  a  failure  of  outlet  temp.  sensor, 

the heating is blocked

contact an authorised service or the seller 

G indicator flickers, 

master appliance 

doesn’t work 

a  failure  of  installation  that  con-

nects the master appliance

contact an authorised service or the seller

a failure of electronic module

contact an authorised service or the seller

EKCO.LN2 and 

EKCO.L2 model 

doesn’t heat the 

cylinder

a failure of cylinder temp. sensor 

or thermostat  

contact an authorised service, replace cyl-

inder temp. sensor or thermostat

a failure of three-way  valve ser-

vo-motor

replace servo-motor

a failure of electronic module 

contact an authorised service or the seller

EE message on E 

display

data record error 

contact an authorised service or the seller

Summary of Contents for EKCO.LN2

Page 1: ...ELECTRIC CENTRAL HEATING FLOW BOILER QuickTec GmbH Bardelebenweg 25 14089 Berlin Germany Tel 49 0 30 577 01 88 40 Fax 49 0 30 577 01 88 49 E Mail mail quick tec com quick tec com...

Page 2: ...for recycling Appropriate utilisation of used product prevents potential negative environmental influences that may occur as a result of inappropriate handling of waste In order to get more detailed...

Page 3: ...l is equipped with a differential pressure relief valve bypass It allows the system to keep minimal flow of heating medium through the boiler and reduce noises in installation during the thermostatic...

Page 4: ...entry 8 Once you have finished the above procedures you can start the boiler See the Start up section While applying thermostat make sure there is no voltage on its entry Do not connect any voltage i...

Page 5: ...xtra expansion vessel should be installed on it Temperature of heating medium feed and return Capacity of central heating system Pressure in central heating system C l bar 85 70 58 1 5 70 55 79 55 45...

Page 6: ...not run close to mains cables they must not go around other electric wires Important To activate the sensor and DHW cylinder heating please follow the in structions in section ADVANCED SETTINGS Set up...

Page 7: ...try so that when a master appliance gets on the contact will be opened the boiler switched off When the NA contact gets opened heating will get off and the pump stopped The EKCO LN2 and EKCO L2 model...

Page 8: ...n the table below set the appropri ate mode according to the following instructions press button for longer than 2 seconds but less than 10 seconds LED s will start to flash the pump then switches to...

Page 9: ...external external thermostat the close open contact is connected to Tzas entry If the DHW cylinder mode is inactive this parameter is unavailable installation pressure sensor active 1 or inactive 0 i...

Page 10: ...nt Do not cut power supply off between heating season When the control panel is switched to Stand by mode the control panel is off the F icons flickers only In this mode the boiler is off but the pump...

Page 11: ...ing system is off When and icons are on it shows that the boiler is in C H DHW mode When you switch to this mode the control panel is in the main view display an icons show current working mode The di...

Page 12: ...r is on inlet temp D and K indicators are on outlet temp D and L indicators are on medium flow rate through the boiler B indicator is on pressure in the system A indicator is on power with which the b...

Page 13: ...CO L2 boiler heats the DHW icon is on all models temp in CH system is lower than required but the required room temperature has been reached RP entry is open or room thermostat is blocked EKCO LN2 EKC...

Page 14: ...act an authorised service or the seller G indicator is off in winter mode a failure of installation that con nect a room thermostat contact an authorised service or the seller a failure of electronic...

Page 15: ...0 27 0 17 0 15 0 27 Rated power kW 12 15 18 21 24 Rated voltage 400V 3N Rated current A 3x17 3 3x21 7 3x26 0 3x30 3 3x34 6 Fuse rated current A 20 25 32 40 Min connecting wires section mm2 5 x 2 5 5...

Page 16: ...QuickTec GmbH Bardelebenweg 25 14089 Berlin Germany Tel 49 0 30 577 01 88 40 Fax 49 0 30 577 01 88 49 E Mail mail quick tec com quick tec com...

Reviews: