background image

7

GB-031AB/f.

DHW Cylinder thermostat (Tzas entry- refers to EKCO.LN2 and EKCO.L2 model) 

– 

Kospel suggests to use the VCZMH6000E valve with the VC6013ZZ00 servo-motor. The 

three-way valve control is performed by applying 230V on the brown wire or the black 

wire (blue is the neutral wire). Voltage on the valve through the brown wire will switch the 

valve to a position, where the pass between the „AB” inlet and the „B” outlet gets opened. 

Shall voltage be passed to the black wire, the valve will get switched to the position in 

which the channel between the „AB” inlet and the „A” outlet will be opened. The „AB” 

inlet and the „A” and „B” outlets are marked on the valve An entry „B’’ is to supply the 

central heating system and the entry „A’’ is to supply the cylinder. Important. To activate 

the cylinder heating please follow the instructions in the „ADVANCED SETTINGS” sec-

tion. Set up the temperature of heating medium (50 - 85°C).

Master appliance (NA entry)

 – you can limit the power used, i.e. the boiler can be 

switched off while another appliance consumes electricity. To do it, an electrician should 

install in line an extra open contact to the NA entry (voltage free entry), so that when a 

master appliance gets on, the contact will be opened the boiler switched off. When the 

NA contact gets opened, heating will get off and the pump stopped. The EKCO.LN2 

and EKCO.L2 model may also work as second boiler. If it is so, the master boiler by 

opening the NA entry will stop heating of EKCO. However, the mode of the three-way 

valve control stays on so a DHW cylinder is charged by the heat from the master boiler.

refers to EKCO.LN2 and EKCO.L2 boiler only

Special start-up procedure (when the system is filled with an antifreeze solution)

A flow rate reading error may occur if you start-up the unit at low ambient temperature. 

This error may occur because the physical properties of antifreeze solution. If the H 

indicator flickers and the cut-off valves are opened you have to close NA and RP contacts 

which will automatically start the special start-up procedure. As a result, the medium will 

be warmed up to temperature that enable you to read the flow rate correctly. The duration 

of procedure depends on both the installation capacity and the temperature inside the 

installation. When a control panel display shows selected parameters alternately and 

marks („-”, „--”) it means that the procedure is started. The procedure will close auto-

matically and the unit will start normal operation once the minimal flow rate is reached.

Summary of Contents for EKCO.LN2

Page 1: ...ELECTRIC CENTRAL HEATING FLOW BOILER QuickTec GmbH Bardelebenweg 25 14089 Berlin Germany Tel 49 0 30 577 01 88 40 Fax 49 0 30 577 01 88 49 E Mail mail quick tec com quick tec com...

Page 2: ...for recycling Appropriate utilisation of used product prevents potential negative environmental influences that may occur as a result of inappropriate handling of waste In order to get more detailed...

Page 3: ...l is equipped with a differential pressure relief valve bypass It allows the system to keep minimal flow of heating medium through the boiler and reduce noises in installation during the thermostatic...

Page 4: ...entry 8 Once you have finished the above procedures you can start the boiler See the Start up section While applying thermostat make sure there is no voltage on its entry Do not connect any voltage i...

Page 5: ...xtra expansion vessel should be installed on it Temperature of heating medium feed and return Capacity of central heating system Pressure in central heating system C l bar 85 70 58 1 5 70 55 79 55 45...

Page 6: ...not run close to mains cables they must not go around other electric wires Important To activate the sensor and DHW cylinder heating please follow the in structions in section ADVANCED SETTINGS Set up...

Page 7: ...try so that when a master appliance gets on the contact will be opened the boiler switched off When the NA contact gets opened heating will get off and the pump stopped The EKCO LN2 and EKCO L2 model...

Page 8: ...n the table below set the appropri ate mode according to the following instructions press button for longer than 2 seconds but less than 10 seconds LED s will start to flash the pump then switches to...

Page 9: ...external external thermostat the close open contact is connected to Tzas entry If the DHW cylinder mode is inactive this parameter is unavailable installation pressure sensor active 1 or inactive 0 i...

Page 10: ...nt Do not cut power supply off between heating season When the control panel is switched to Stand by mode the control panel is off the F icons flickers only In this mode the boiler is off but the pump...

Page 11: ...ing system is off When and icons are on it shows that the boiler is in C H DHW mode When you switch to this mode the control panel is in the main view display an icons show current working mode The di...

Page 12: ...r is on inlet temp D and K indicators are on outlet temp D and L indicators are on medium flow rate through the boiler B indicator is on pressure in the system A indicator is on power with which the b...

Page 13: ...CO L2 boiler heats the DHW icon is on all models temp in CH system is lower than required but the required room temperature has been reached RP entry is open or room thermostat is blocked EKCO LN2 EKC...

Page 14: ...act an authorised service or the seller G indicator is off in winter mode a failure of installation that con nect a room thermostat contact an authorised service or the seller a failure of electronic...

Page 15: ...0 27 0 17 0 15 0 27 Rated power kW 12 15 18 21 24 Rated voltage 400V 3N Rated current A 3x17 3 3x21 7 3x26 0 3x30 3 3x34 6 Fuse rated current A 20 25 32 40 Min connecting wires section mm2 5 x 2 5 5...

Page 16: ...QuickTec GmbH Bardelebenweg 25 14089 Berlin Germany Tel 49 0 30 577 01 88 40 Fax 49 0 30 577 01 88 49 E Mail mail quick tec com quick tec com...

Reviews: