3. CALIFORNIA HERS RA3.9.4.1.2 FOR WHF AIRFLOW MEASUREMENT

IMPORTANT:

 Read this before equipment setup!

IMPORTANT: 

For proper usage as a powered flow hood for testing airflow, please refer to

Reference Appendices RA3.9.4.1.2. This device is designed to be compliant with that protocol.

The WHF-PFH is approved to be used with the Retrotec 5000/6000 series blower door fans, 

and TEC Model 3 110V series blower door.

NOTE: Retrotec 5000 series will only work with the WHF-PFH to measure up to 4500 CFM

The WHF airflow measurement shall be performed using the following procedures:

1.  Open the window(s) that are typically opened during WHF operation.

2.  Turn on all WHFs required to meet the dwelling unit WHF airflow rate. Adjust multiple or 

variable speed WHFs to operate at an airflow rate that will be greater than or equal to the 

rate required for compliance.

3.  Adjust the dwelling unit window openings to bring the dwelling unit to the WHF-OP of 

negative 10 Pa 

±

 5 Pa WRT outside.

4.  Measure the airflow rate(s) at the inlet grille(s) with a calibrated powered flow hood to 

determine the total WHF airflow for the dwelling unit.

No part of the WHF intake shall be blocked or masked off to accommodate an undersized hood.

Operation of the powered flow hood shall conform to the specifications in the manufacturer’s

product documentation.

Summary of Contents for WHF-PFH

Page 1: ...OPERATION MANUAL HERS POWERED FLOW HOOD MODEL WHF PFH MAKERS OF THE QUIETCOOL ADVANCED WHOLE HOUSE FAN...

Page 2: ...ce personnel should service the system The user should not attempt to service the product 6 Maneuvering the Unit When lifting stand or moving the unit around the house be very careful not to drag it a...

Page 3: ...Velcro iv Coroplast rectangular cutout v Soft plastic tubing with 4 barbed tee fittings pressure taps vi Fiberglass poles QTY 4 Bottom square Frame 27 5 x 27 5 Top Octagonal Frame Telescoping Legs i 4...

Page 4: ...Do not route cord under furniture or appliances Arrange cord away from traffic area and where it will not be tripped over Do not place this equipment or power cord in water or other liquid Use only t...

Page 5: ...needs to be between 4 5 from ceiling ii It is recommended to adjust height of legs prior to adding top octagonal frame c FOR RETROTEC FANS i Slide Retrotec fan in between the 4 legs See pictures below...

Page 6: ...completely or test may yield inaccurate results 4 Ensure hood is flush by lightly pushing up on bottom of hood a If you see the top of hood move readjust poles by going higher b Check again and repeat...

Page 7: ...Gauge 1 Take the pressure tap coming out the bottom of the flow hood and connect it to the input tap to read pressure 2 See page 9 for complete connection details Complete WHF PFH with TEC Model 3 Fa...

Page 8: ...procedures 1 Open the window s that are typically opened during WHF operation 2 Turn on all WHFs required to meet the dwelling unit WHF airflow rate Adjust multiple or variable speed WHFs to operate...

Page 9: ...he channel A pressure channel reference tap open to read pressure inside the dwelling 5 On TEC Model 3 fan connect the pressure tap from the blower door fan to the channel B flow channel input tap 6 O...

Page 10: ...e airflow Verify all tube connections are properly connected for airflow measurement apparatus and hood adapter system Ensure proper connection of the WHF PFH flow hood to testing fan apparatus has a...

Page 11: ...ow rate listed on CF 1R report Title 24 reports that have modeled medium speeds for 2019 code only need to be tested at medium speed If the measured flow rate is failing too low try running WHF at a h...

Page 12: ...12 Rev 6 11 20 MAKERS OF THE QUIETCOOL ADVANCED WHOLE HOUSE FAN...

Reviews: