Controller Function Manual and Operating Method

Controller Function

The unit for temperature is centigrade in this function manual. If there's Fahrenheit, the transition relation is 

TFahrenheit =TCentigrade  1.8+32.  

Temperature Parameter

Indoor ambient temperature (T

amb.

Indoor copper tube temperature (T

tube

Evaporator inlet pipe temperature (T

inlet pipe

Evaporator outlet pipe temperature (T

outlet pipe

System Basic Functio

n

2.1 Cooling Mode 

 

(1) Fan motor and swing works under setting status 

(2) Indoor unit will run under the original status when outdoor unit malfunction or stop to run protection, malfunction 

displays. 

(3) The fan motor stops when the modes conflicts. 

      The temperature setting range is 60.8-86  under the mode. 

 

2.2 Dry Mode 

(1) Fan motor runs under low speed, swing runs by setting status. 

(2) Indoor unit will run under the original status when outdoor unit malfunction or stop to run protection, malfunction 

displays. 

      The temperature setting range is 60.8-86  under the mode. 

 

2.3 Fan Mode 

In this mode, only indoor fan is running at setting status. Under auto fan speed, it will run by cooling auto fan. 

 

2.4 Heating Mode 

(1) The indoor unit goes to anti-cool wind when the unit is ON; it goes to blow residual heat when the unit is OFF and

 

indoor fan motor was ON before. 

(2) Protection function, compressor is OFF as malfunction (including any temperature sensor malfunction), indoor fan

 

motor runs with blowing residual heat. 

(3) Anti-cool wind: indoor fan motor runs after 2 minutes delayed. 

      Blow residual heat: the indoor unit runs 60S with the original fan speed then stop; the fan speed cannot shift and

 

the guide board changes to the heating minimum angle when blowing residual heat. 

(4) Indoor fan motor stops and does not blow residual under defrost and oil return; the temperature sensor of indoor

 

unit cannot be inspected during defrost, oil return and exit in 3min process. 

      The temperature setting range is 60.8-86  under the mode. 

 

2.5 Auto Mode 

In this mode, the unit will select the cooling, heating running mode or fan mode automatically according to the change

 

of ambient temperature. Protection function is the same as that in heating, cooling mode. 

 

2.6 Mode Clash 

When the indoor receiving the information mode clash from outdoor unit and the digit is 1, the indoor load (indoor fan

 

motor, swing) stops, the malfunction indicator displays, the mode send to outdoor unit is the mode receiving by remote 

control.  

When the time of TIMER ON reach, if the indoor receiving the information mode clash from outdoor unit and the digit is 

1, the indoor load (indoor fan motor, swing) stops, the malfunction indicator displays, the mode send to outdoor unit is 

the mode receiving by remote control. 

 

3. Others 

3.1 Buzzer 

   When the controller energized, receiving signal from remote controller and auto button, the buzzer will give out

 

beep. 

 

3.2 Auto Button 

      Press the button when turn off the unit, the unit runs by auto mode, indoor fan motor runs under auto fan speed, 

turn on swing. Press auto button under the unit is ON, it will OFF. 

 

3.3 Auto Fan Speed Control 

   Under cooling, heating, fan mode, the indoor fan motor will select the high, med, low fan speed automatically 

according to the change of ambient temperature, the auto fan speed is low speed under FAN mode. The spacing of

 

shift each fan speed is 3.5 min. 

 

3.4 Sleep 

O

F

O

F

O

F

Summary of Contents for QSVMI-09A

Page 1: ...1 Summary and features Summary and features Model Service Manual QSVMI 09A QSVMI 12A QSVMI 18A ...

Page 2: ......

Page 3: ...gth l x height H x coil width L inch 22 83X8 98X1 22 83X8 98X1 26 81X12 76X1 5 Swing Motor Model MP28VB MP28VB MP28EC Output of Swing Motor W 2 2 2 Fuse A PCB 3 15A Transformer 0 2A PCB 3 15A Transformer 0 2A PCB 3 15A Transformer 0 2A Sound Pressure Level dB A H M L 37 34 31 28 38 34 31 28 40 34 32 30 Sound Power Level dB A H M L 47 44 41 38 48 44 41 38 50 44 42 40 Dimension W H D inch 30 32X9 84...

Page 4: ... board Air out Remote control Heating Cooling Setting temp Auto Power Run Fan Dehumidify Remote control receiving window Water drainage pipe Connection pipe and connection wire Wrapping tape Amplified sketch for displayer Part name Part name 3 ...

Page 5: ...let pipe hole Top view diagram Mark for right outlet pipe hole Back view Ceiling 4 Outline and installation dimension Outline and installation dimension QSVMI 09A QSVMI 12A 9 84 inch 30 32 inch 7 48 inch 7 87 inch 2 76 inch 7 87 inch ...

Page 6: ...Air inlet grid Mark for left outlet pipe hole Top view diagram Mark for right outlet pipe hole Back view Ceiling QSVMI 18A 11 22 inch 32 68 inch 7 87 inch 7 87 inch 2 76 inch 7 87 inch ...

Page 7: ...Electrical circuit diagram Electrical circuit diagram 5 5 5 5 5 These circuit diagrams are subject to change without notice please refer to the one supplied with the unit QSVMI 09A QSVMI 12A QSVMI 18A ...

Page 8: ... fan speed then stop the fan speed cannot shift and the guide board changes to the heating minimum angle when blowing residual heat 4 Indoor fan motor stops and does not blow residual under defrost and oil return the temperature sensor of indoor unit cannot be inspected during defrost oil return and exit in 3min process The temperature setting range is 60 8 86 under the mode 2 5 Auto Mode In this ...

Page 9: ...ng timer function in the last remote control order and the system memory the last remote control order and working under that setting method There is general timer function in the last remote control order the system is energized before the timer time haven t reach the unit will memory timer function of the last remote control order after re energized and the timer time will star to calculate afte...

Page 10: ...Display Running Lamp Heating Lamp Cooling Lamp The system is abnormal anti high temp power off cooling overload H4 Blink 4 times Compressor overload protection H3 Blink 3 times Module protection H5 Blink 5 times High pressure protection E1 Blink once Anti freeze protection power off E2 Blink Twice Discharge temperature protection E4 Blink 4 times Low voltage over current protection E5 Blink 5 time...

Page 11: ...ixing the panel of the panel body to remove the panel Disassemble Cope of Electric Box Firstly screw off the screw fixing the cope of electric box open the cope of electric box loose the clasp and remove the cope of electric box Disassemble Filter Push the filter inward and then pull it upward to remove it Protection plate Panel the cope of electric box clasp Filter Screws Dissassembly Procedures ...

Page 12: ...move the upper guide louver Guide Louver clasp Disassemble Front Case Unscrew the three screw covers at the front case unscrew the three screws pull open the clasp at the front case and remove the front case clasp sensor screw covers screws Disassemble Water Tray Screw off the fixing screws fixing the water tray with a screw driver Loose the clasp at the other end and pull out the terminal board o...

Page 13: ... screwdriver to unscrew the screw fixing the electric box loose the clasp and remove the electric box pipe temp sensor room sensor grounding wire plugging connector clasp screw Disassemble Evaporator rear pipe clamp screw Screw off one screw which fix the connection board clamp Take down the connection board clamp Screw off 4 screws fixing the left and right side of the evaporator then elevate lef...

Page 14: ...screw screw Evaporator Disassemble Motor Use screwdriver to unscrew the two screws fixing the motor clamp and remove the motor clamp Unscrew the three holding screws at the shaft sleeve and remove the motor motor clamp Screw screw Motor Axial fan ...

Page 15: ...Disassemble Cross Flow Fan After remove the motor pull out it from the left bearing holder Cross Flow Fan Bearing Holder Operating Procedures Photos ...

Page 16: ...8 Explosive view and spare parts list Explosive view and spare parts list Exploded View of Component 1 ...

Page 17: ... 1 29 Room Sensor15K 1 1 1 1 31 Jumping Connector 1 32 Transformer 48X26P 1 33 Wire clamp 1 34 Rear clamp 1 35 Connecting Cable 1 36 swing louver clamp 1 37 swing louver 1 38 swing louver up 1 39 swing louver down 1 Qty Part Code 30 Tube Sensor 20K No Description QSVMI 09A 01252220 222020016 010020534 10352001 76512203 0523001401 201820270 10512088 10582002 10582003 200022107 200022092C 68012019 3...

Page 18: ... Exploded View of Component 2 ...

Page 19: ... 200022921 1 18 Guide Louver 261120432 1 19 Guide Louver 261120422 1 20 Motor MP28EC 15212002 1 21 22 23 Right Motor Clamp 26112429 1 24 Bearing Holder 26152423 1 25 Motor FN20M PG 150120873 1 26 Electric Box Cover 20122081 1 27 Terminal Board T4B3A 42011233 1 28 Covering Plate 20112060 1 29 Electric Box 20112059 1 30 Main PCB M803F2AJ 30038004 1 31 Transformer 48X26P 43110293 1 32 Wire Clamp 7101...

Page 20: ...Exploded View of Component 3 ...

Page 21: ...ight Board 22432071 1 20 Electric Box Cover 1 20112019 1 21 Wire Clamp 71010103 1 22 Terminal Board 3位 4201026601 1 23 Electric Box Cover 20112020 1 24 Main PCB 30038022 1 25 Transformer 57X25F 43110257 1 26 Room Sensor 15k 390001912 1 3900019814 1 3900019815 1 3900019816 1 28 Sensor Insert 42020063 3 29 Electric Box 20112018 1 30 Lower Shield of Electric Box 01592037 1 31 Upper Shield of Electric...

Page 22: ......

Page 23: ......

Page 24: ...nta Fe Springs CA 90670 USA Phone 562 699 6066 Fax 562 699 4351 East Office 6 Pine Hill Drive Carlisle PA 17013 Phone 886 243 6498 717 243 2535 Fax 717 243 7917 TX Office 3001 Northern Cross Blvd Suite 361 Fort Worth TX 76137 Phone 817 838 6066 Fax 817 838 8670 66129908658 ...

Reviews: