background image

1.5

Safety precautions during maintenance or repair

Precautions during maintenance or repair

1. Always use the correct safety equipment (such as safety glasses, gloves, safety shoes, etc.).
2. Use only the correct tools for maintenance and repair work.
3. Use only genuine spare parts.
4. All maintenance work shall only be undertaken when the machine has cooled down.
5. A warning sign bearing a legend such as "Work in progress - do not start" shall be attached to the starting

equipment.

6. Persons switching on remotely controlled machines shall take adequate precautions to ensure that there

is no one checking or working on the machine. To this end, a suitable notice shall be affixed to the remote
starting equipment.

7. Close the dryer air outlet valve before connecting or disconnecting a pipe.
8. Before removing any pressurized component, effectively isolate the machine from all sources of pressure

and relieve the entire system of pressure.

9. Never use flammable solvents or carbon tetrachloride for cleaning parts. Take safety precautions against

toxic vapours of cleaning liquids.

10. Scrupulously observe cleanliness during maintenance and repair. Keep dirt away by covering the parts

and exposed openings with a clean cloth, paper or tape.

11. Never weld on, or in any way modify, pressure vessels.
12. Whenever there is an indication or any suspicion that an internal part of a machine is overheated, the

machine shall be stopped but no inspection covers shall be opened before sufficient cooling time has
elapsed; this to avoid the risk of spontaneous ignition of the oil vapor when air is admitted.

13. Never use a light source with open flame for inspecting the interior of a machine, pressure vessel, etc.
14. Make sure that no tools, loose parts or rags are left in or on the machine.
15. All regulating and safety devices shall be maintained with due care to ensure that they function properly.

They may not be put out of action.

16. Before clearing the machine for use after maintenance or overhaul, check that operating pressures,

temperatures and time settings are correct. Check that all control and shut-down devices are fitted and that
they function correctly.

17. Protect the motor, electrical and regulating components, etc. to prevent moisture from entering them, e.g.

when steam-cleaning.

18. Make sure that all sound-damping material and vibration dampers, e.g. damping material on the bodywork,

is in good condition. If damaged, replace it by genuine material from the manufacturer to prevent the
sound pressure level from increasing.

19. Never use caustic solvents which can damage materials of the air net, e.g. polycarbonate bowls.
20.

The following safety precautions are stressed when handling refrigerant:

• Never inhale refrigerant vapours. Check that the working area is adequately ventilated; if required, use

breathing protection.

• Always wear special gloves. In case of refrigerant contact with the skin, rinse the skin with water. If

liquid refrigerant contacts the skin through clothing, never tear off or remove the latter; flush
abundantly with fresh water over the clothing until all refrigerant is flushed away; then seek medical
first aid.

21.

The following safety precautions are stressed when handling desiccant:

• Take precautions not to inhale desiccant dust.
• Check that the working area is adequately ventilated; if required, use breathing protection.
• Do not overfill the dryer when replacing desiccant.

Instruction book

8

2920 7103 90

Summary of Contents for QED-250

Page 1: ...Quincy Refrigerant compressed air dryers QED 300 QED 600 QED 450 QED 250 QED 350 QED 500 Instruction book...

Page 2: ......

Page 3: ...or copying of the contents or any part thereof is prohibited This applies in particular to trademarks model denominations part numbers and drawings This instruction book is valid for CE as well as no...

Page 4: ...CONDENSATE DRAIN SYSTEM 15 3 Controller 17 3 1 INFOLOGIC CONTROLLER 17 3 2 CONTROL PANEL 18 3 3 ICONS AND SYMBOLS USED ON THE DISPLAY 18 3 4 MAIN SCREEN 20 3 5 SCROLLING THROUGH ALL SCREENS 20 3 6 CAL...

Page 5: ...24 ACTIVATING PASSWORD PROTECTION 34 3 25 SELECTION BETWEEN FLEXIBLE ALARM AND FIXED ALARM 35 3 26 CALLING UP MODIFYING FIXED DEW POINT ALARM SETTING 35 3 27 CALLING UP MODIFYING FLEXIBLE DEW POINT A...

Page 6: ...ng 53 8 Technical data 57 8 1 SETTINGS OF FUSES 57 8 2 REFERENCE CONDITIONS AND LIMITATIONS 57 8 3 AIR DRYER DATA 58 9 Pressure equipment directives 60 10 Declaration of conformity 61 Instruction book...

Page 7: ...trained specialized personnel 5 The dryer is not considered capable of producing air of breathing quality To obtain air of breathing quality the compressed air must be adequately purified according to...

Page 8: ...olled machines shall take adequate precautions to ensure that there is no one checking or working on the machine To this end a suitable notice shall be affixed to the starting equipment 10 Air cooled...

Page 9: ...g to carry out routine checks Wear ear protectors when removing a panel 7 People staying in environments or rooms where the sound pressure level reaches or exceeds 90 dB A shall wear ear protectors 8...

Page 10: ...source with open flame for inspecting the interior of a machine pressure vessel etc 14 Make sure that no tools loose parts or rags are left in or on the machine 15 All regulating and safety devices sh...

Page 11: ...ply to machinery processing or consuming air or inert gas Processing of any other gas requires additional safety precautions typical to the application which are not included herein Some precautions a...

Page 12: ...point This causes the water to condense The condensate is automatically drained The dried air is warmed up before leaving the dryer An Infologic controller controls and protects the dryer QED 250 up t...

Page 13: ...600 side view The front panel and the side panel can be removed for service operations Reference Designation 1 Supply cable passage Dm Manual drain valve Da Automatic drain connection Instruction boo...

Page 14: ...250 up to QED 600 internal view Reference Name 1 Compressor 2 Condenser 3 Heat exchanger 4 Condenser fan 5 Hot gas bypass valve 6 Capillary tube 7 Refrigerant dryer filter Instruction book 12 2920 710...

Page 15: ...The air then flows through heat exchanger evaporator 2 where the refrigerant evaporates causing the air to be further cooled to close to the evaporating temperature of the refrigerant More water in th...

Page 16: ...erant dryer filter 8 Capillary 9 Electronic condensate drain 10 Liquid separator 11 Cooling fan Dm Manual drain valve Operation The liquid separator 10 ensures that only refrigerant enters the compres...

Page 17: ...der partial or no load the evaporator pressure drops to 7 3 bar e 105 8 psig the bypass regulator 5 opens and hot high pressure gas is fed to the evaporator circuit to prevent the evaporator pressure...

Page 18: ...alve will make a short forced opening every three hours LED L2 indicates an alarm situation The test button can be used in three different ways When it is pressed during normal operation it starts a m...

Page 19: ...when required Allows selection of the control mode See section Calling up modifying dryer regulation mode In order to control the dryer and to read and modify programmable parameters the controller ha...

Page 20: ...switched on 8 Service symbol 9 LED Service Is lit when service is needed 10 Start button This button starts the dryer Automatic operation LED 3 lights up The Infologic is operative 11 Stop button Thi...

Page 21: ...er is active Service Service required Units Temperature unit Temperature unit Hours The value shown must be multiplied by 1000 to get the actual value Other icons Motor Drain Flow switch on energy sav...

Page 22: ...icon is displayed during a programmed time After this period the timer icon disappears again 3 5 Scrolling through all screens Scroll buttons Scroll buttons 12 can be used to scroll through all scree...

Page 23: ...e timer settings P 5 Setting of the temperature unit See section Calling up Modifying unit of temperature P 6 Setting of the pressure unit See section Calling up Modifying unit of pressure P 7 Functio...

Page 24: ...Description 1 Dew point main screen 13 Temperature unit 2 Ambient temperature 14 Pressure unit 3 Digital input status 15 Auto restart function 4 Running hours 16 Dryer regulation mode 5 Motor starts...

Page 25: ...the ambient temperature is 25 C 77 F This temperature is used by the regulation algorithm to calculate a safe dew point in the energy efficient mode see section Calling up modifying dryer regulation m...

Page 26: ...r in x1000 hrs hours x 1000 In above example the screen shows the dryer has been running during 100 hours 3 9 Calling up motor starts Calling up motor starts This screen shows the number of motor star...

Page 27: ...Service warning A service warning will appear when the service timer has reached the programmed time interval See section Calling up modifying service timer settings If the service timer exceeds the p...

Page 28: ...een with dew point temperature warning In the example shown the dew point is 20 C 68 F and the dew point icon is flashing If the dew point becomes normal again the alarm will disappear High ambient te...

Page 29: ...pear as soon as the warning condition disappears 3 13 Shut down Description The dryer will shut down In case the dew point temperature gets below 0 5 C 31 1 F delay 30 s In case the ambient temperatur...

Page 30: ...AN control To change press Enter button 13 and if necessary enter the password see section Activating password protection The actually selected control mode is blinking Use Scroll button 12 to change...

Page 31: ...ed Change the function to OFF to change the node ID It is also possible to change the channels The controller has 4 channels When changing the channels the controller can act as a Mk IV controller a p...

Page 32: ...Enter button 13 to modify it to OFF Use the Scroll buttons Up or Down 12 to scroll between the items in this list IP for IP address Sub for Subnetmask or GAtE for Gateway Modification Press the Enter...

Page 33: ...Press Enter button 13 to modify this value a password may be required the value starts blinking Use the Scroll buttons 12 to modify the setting Press Enter button 13 to program the new value Press Es...

Page 34: ...yer regulation mode Description The dryer has two regulation modes Regular mode The dryer achieves the lowest possible dew point Energy efficient mode The dryer will regulate the dew point between the...

Page 35: ...and then press Enter key 13 the actual flow switch setting is shown StOP flow switch function is active or OFF flow switch function is not active Press Enter key 13 to modify this value a password may...

Page 36: ...ce timer and control mode settings can be protected by a password Starting from the Main screen Press Scroll buttons 12 until P 10 is shown and press Enter button 13 Password PASS appears on the scree...

Page 37: ...is blinking Use Scroll button 12 to change the alarm mode Press Enter button 13 to program the new alarm mode Press Escape button 14 to return to the parameter screens 3 26 Calling up modifying fixed...

Page 38: ...difying the low dew point setting Calling up modifying the low dew point setting In protection parameter set Pr 2 the Low dew point alarm level AL L and the Low dew point shutdown level Sd L can be se...

Page 39: ...95 F and 60 C 140 F Starting from the Main screen press Scroll button 12 until Pr 3 is shown and then press Enter button 13 AL H is shown Press Enter button 13 the programmed value starts blinking Use...

Page 40: ...4 Installation 4 1 Dimension drawings QED 250 and QED 300 dimension drawing Instruction book 38 2920 7103 90...

Page 41: ...350 up to QED 600 dimension drawing Reference Name 1 Main supply electrical cable gland M25 2 Manual drain 3 Automatic drain 4 Cooling air flow 5 Air inlet 6 Air outlet Instruction book 2920 7103 90...

Page 42: ...4 2 Installation proposal Installation proposal QED 250 and QED 300 Instruction book 40 2920 7103 90...

Page 43: ...Installation proposal QED 350 up to QED 600 Text on drawings Instruction book 2920 7103 90 41...

Page 44: ...3 Make sure that no dirt particles e g coming from corrosion in the compressed air network can enter the dryer These particles may be harmful to the dryer s heat exchanger and the condensate drain 4 I...

Page 45: ...3 Check the fuses and the setting of the overload relay See section Settings of fuses 4 On single phase units connect the power supply cables to terminals L1 L2 of terminal strip 1X0 5 On three phase...

Page 46: ...units Typical designations used in the electrical diagrams Reference Designation 1 Customer s installation 2 Flow switch 3 Alarm EWD 4 Remote start stop B1 Electronic drain 1X0 6 Terminals F1 6 Fuses...

Page 47: ...ase sequence relay K5 Auxiliary relay alarm functions M1 Compressor M2 Fan motor PSHH13 High pressure switch PSR12 Fan switch S1 Remote start stop S2 Flow switch X209 Connector 4 4 Pictographs Pictogr...

Page 48: ...Reference Description 5 Warning voltage 6 Information label refrigerant Contains fluorinated greenhouse gases covered by the Kyoto Protocol Instruction book 46 2920 7103 90...

Page 49: ...2 Initial start Procedure Control panel Step Action 1 A few minutes before starting the main supply to the dryer must be switched on to initialize the Infologic and the flow switch 2 Press start butto...

Page 50: ...nd the flow switch to initialize 2 If installed close the dryer bypass valve and the dryer outlet valve customers installation 3 Open the dryer air inlet valve customers installation and pressurize th...

Page 51: ...display of the control panel The pressure dew point will deviate from nominal if the air inlet conditions or volume flow differ from nominal That condensate is discharged The amount depends on the op...

Page 52: ...1 Close dryer inlet and outlet valves customer s installation 2 Press stop button 11 The dryer stops Voltage on LED 4 remains lit Leave the voltage on if the dryer has to remain on stand by Instructio...

Page 53: ...can reach a temperature of 110 C 230 F Therefore wait until the dryer has cooled down before removing the panels Before starting any maintenance or repair work switch off the voltage and close the ai...

Page 54: ...off the supply voltage Remove the front service panel Remove dust from the condenser surface using a vacuum cleaner Clean the condenser by blowing compressed air from outside to inside Keep the compre...

Page 55: ...ceeded Reduce air flow Shortage of refrigerant Have circuit checked for leaks and have the refrigerant circuit recharged Condition Fault Remedy Condenser pressure too high or too low Fan control switc...

Page 56: ...m visible red light and blinking drain icon Condition Fault Remedy Drain alarm No pressure in the air net Error disappears when the pressure in the air net is restored Drain was not able to drain all...

Page 57: ...ing K12 1 K12 3 Condition Fault Remedy High pressure switch has shut down the dryer Condensing pressure too high Push the small button of the high pressure switch Clean condenser Improve ventilation o...

Page 58: ...ow the minimum pressure Ensure there is the minimum pressure The drain filter is blocked by dirt Open the manual drain valve to clean the drain filter The feed and or outlet line is shut off or blocke...

Page 59: ...ons Unit 60 Hz Compressed air inlet pressure bar e 7 Compressed air inlet pressure psig 101 53 Compressed air inlet temperature C 38 Compressed air inlet temperature F 100 4 Ambient temperature C 38 A...

Page 60: ...l power consumption including cooling fan 60 Hz kW 1 5 1 5 2 3 Total power consumption including cooling fan 60 Hz hp 2 28 3 22 3 08 Refrigerant type R410a R410a R410a Refrigerant charge approx kg 0 8...

Page 61: ...Air dryer type Units QED 450 QED 500 QED 600 Dryer mass approx kg 197 197 197 Dryer mass approx lb 434 434 434 Instruction book 2920 7103 90 59...

Page 62: ...an or equal to category II Dryer type Part number Description PED Class QED 250 up to QED 600 1089 9139 14 High pressure switch IV QED 250 and QED 300 1624 2274 00 Heat exchanger II QED 350 1624 2275...

Page 63: ...laration of conformity Typical example of a Declaration of Conformity document 1 Contact address Quincy Compressor 701 North Dobson Avenue Bay minette AL 36507 United States Instruction book 2920 7103...

Page 64: ......

Page 65: ......

Page 66: ...No 2920 7103 90 2011 11 Printed in Belgium Performance You Demand Reliability You Trust www quincycompressor com...

Reviews: