Instruction Book
9828 0934 73
119
Unit
At ambient temperature of:
°F
100
77
86
95
104
At ambient temperature of:
°C
38
25
30
35
40
Volume flow at dryer inlet
under nominal conditions
cfm
869
869
869
869
869
Volume flow at dryer inlet
under nominal conditions
l/s
410
410
410
410
410
Pressure dew-point
˚F
43
37
45
57
70
Pressure dew-point
˚C
6
3
7
14
21
Total power consumption
hp
4.4
4.3
4.4
4.6
4.6
Total power consumption
kW
3.3
3.2
3.3
3.4
3.4
Cooling water flow (approx.)
*)
cfm
2.5
2.1
2.5
2.5
2.8
Cooling water flow (approx.)
*)
l/s
1.2
1
1.2
1.2
1.3
Heat dissipated by
cooling water flow
(approx.)
Btu/hr
37600
37600
41000
44400
51200
Heat dissipated by
cooling water flow
kW
11
11
12
13
15
QED-1050 (E
S 510
)
water-cooled, 50 Hz version)
Performance data with cooling water inlet of 25 °C (77 °F)
Unit
At ambient temperature
of:
°C
25
30
35
40
At ambient temperature
of:
°F
77
86
95
104
Volume flow at dryer inlet
under nominal conditions
l/s
510
510
510
510
Volume flow at dryer inlet
under nominal conditions
cfm
1080.63
1080.63
1080.63
1080.63
Pressure dew-point
˚C
2
3
6
12
Pressure dew-point
˚F
35.6
37.4
42.8
53.6
Total power
consumption
kW
4
4
4
4
Total power
consumption
hp
5.36
5.36
5.36
5.36
Cooling water flow
(approx.)
*)
l/s
0.2
0.3
0.3
0.3
Cooling water flow
(approx.)
*)
cfm
0.42
0.64
0.64
0.64
Heat dissipated by cooling
water flow (approx.)
kW
13
16
18
20
Heat dissipated by cooling
water flow (approx.)
Btu/hr
44369
54608
61434
68260