Instruction book
2012 2039 28
124
Code on Q Control
Description on
Q Control
Explanation
Counter measure
Hexadecimal
notation
Decimal
notation
0x6104
24836
Drive failure
(hardware)
Internal checksum
error detected
0x6105
24837
Drive failure
(hardware)
Internal
communication
timeout
0x6106
24838
Drive failure
(hardware)
Internal checksum
error detected
0x6107
24839
Drive failure
(hardware)
Internal
communication
timeout
0x6108
24840
Drive failure
(hardware)
Internal
communication
timeout
0x6109
24841
Drive failure
(hardware)
Internal checksum
error detected
0x610A
24842
Drive failure
(hardware)
Internal
communication
overload
0x610B
24843
Drive failure
(hardware)
Internal control
overload
0x610C
24844
Drive failure
(hardware)
CAN communication
timeout
- Check CAN-cable connection
between Q Control and inverter
- Check position of the CAN
termination switch at both sides
of the CAN cable. Both should
be 'OFF'.
0x610D
24845
Drive failure
(hardware)
Firmware not
compatible
- Try to reset the error
0x610E
24846
Drive failure
(hardware)
Not able to identify
power board
- If error returns, contact service
0x610F
24847
Drive failure
(hardware)
Not able to identify
IGBT module
0x6110
24848
Drive failure
(hardware)
Power board not
compatible with IGBT
modules
0x6111
24849
Drive failure
(software)
Internal CAN state
machine fault
- Check CAN-cable connection
between Q Control and inverter
- Check position of the CAN
termination switch at both sides
of the CAN cable. Both should
be 'OFF'.
0x6112
24850
Drive failure
(software)
Requested command
cannot be executed
because of limited
access level
- Try to reset the error
- If error returns, contact service
0x6113
24851
Drive failure
(software)
CAN communication
overload
- Check CAN-cable connection
between Q Control and inverter
Summary of Contents for QGV 40